EasyManua.ls Logo

Autronica AutroSafe - Connection to Controller Board BSA-400; Common Earth Connections

Autronica AutroSafe
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting External Cables
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 45
10.6.4 Connection to Controller Board BSA-400
The BSA-400 board on all panels provides two separate 10/100Mbit
Ethernet ports. The connector is an RJ-45 modular jack, suitable for
shielded cable CAT5 which allows cable lengths up to 100m.
LED 1
Activity LED
LED 2
If ON, 100MBit/s, if OFF, 10MBit/s
10.6.5 Common Earth Connections
All panels must be connected to a common earth for EMC compliance.
2 x 2
24V
Fire Alarm
Control Panel
BS-420
Controller
BC-420 / BC-440
Power
BPS-410
BU-BV-420
BU-BV-420
Operator
Panel
BS-430
2 x 2
24V
Shielded or armoured cable must be used for the 24V DC power
supply.
Note:
For information on common earth connections for Power Cabinet STX
Range, refer to documentation listed in chapter 6.6.

Table of Contents

Related product manuals