Service and Maintenance
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 60
14. Service and Maintenance
14.1 Introduction
The AutroSafe Interactive Fire Alarm System provides a Log Menu,
which records all system events, i.e. fire alarms, prealarms, faults,
enablements/disablements, user operations and tests.
It is the system owner’s or authorized personnel’s duty to register all
events in a Control Journal.
During service and maintenance of AutroSafe systems, Autronica tools
must be applied.
Note that the system automatically checks all loop units with SelfVerify
functionality every single day (SelfVerify test). This test can also be
performed manually by using the AS2000 Loop Diagnostic Tool.
The loop resistance on the detection loop is continously monitored to
register a possible break or short-circuit on the detection loop. In the
event of a short-circuit in the detector cable, the short-circuit location
will be isolated as the short-circuit isolator will be activated in the
detectors on either side.
For more details regarding the Service Menu, refer to the Menu
Structure and the Operator’s Handbook.
14.2 Monthly Maintenance