Service and Maintenance
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 63
14.7 Safety Measures during Commissioning and
Maintenance
NOTE
To avoid unmotivated activation of release outputs on connected safety-
critical systems, it is important that service personnel physically
disconnects or disables (in the Service Menu) the safety-critical system
from the fire detection system during commissioning and maintenance.
14.8 SIL2 Approved Systems
For SIL2 approved systems, service and maintenance shall be carried
out according to the proof test intervals stated on the AutroSafe 4
Oil&Gas SIL2 (G2) certificate with registration number 44 207 11
555929-001.