Error Code Description Recommended Solution
10054 The Connection to the sensor was
lost while receiving data.
Verify the sensor is energized
Verify the sensor communication cable is connected
Verify all inline network equipment is energized, properly
configured and connected
Verify all required network equipment cables are connected
Verify the network adaptor is properly
configured
Verify the sensor IP address is valid
Verify there are no other devices using the same IP address
Verify the sensor subnet is valid
Verify the sensor can be successfully pinged
Verify the network
firewall settings support connection to the
sensor
10055 The Connection to the sensor was
lost due to network keep alive
expiration.
Verify the network adaptor link speed and duplex settings
Verify the is sensor not stalled, or in shutdown mode
10070 The Connection to sensor was lost
due to a receive state machine
error.
Verify the is sensor not stalled, or in shutdown mode
Verify the sensor is supported by this version
10071 The Connection to sensor was lost
due to a receive state machine
error.
Verify the is sensor not stalled, or in shutdown mode
Verify the sensor is supported by this version
10080 The Connection to sensor was lost. Verify the sensor is energized
Verify the sensor communication cable is connected
Verify all inline network equipment is energized, properly
configured and connected
Verify all required network equipment cables are connected
Verify the network adaptor is properly
configured
Verify the sensor IP address is valid
Verify there are no other devices using the same IP address
Verify the sensor subnet is valid
Verify the sensor can be successfully pinged
Verify the network
firewall settings support connection to the
sensor
10085 A connection to the sensor could
not be established. One or more
required channels failed to connect.
Verify the sensor is energized
Verify the sensor communication cable is connected
Verify all inline network equipment is energized, properly
configured and connected
Verify all required network equipment cables are connected
Verify the network adaptor is properly
configured
Verify the sensor IP address is valid
Verify there are no other devices using the same IP address
Verify the sensor subnet is valid
Verify the sensor can be successfully pinged
Verify the network
firewall settings support connection to the
sensor
10086 The connection to the sensor was
lost while receiving data.
Verify the sensor is energized
Verify the sensor communication cable is connected
Verify all inline network equipment is energized, properly
configured and connected
Verify all required network equipment cables are connected
Verify the network adaptor is properly
configured
Verify the sensor IP address is valid
Verify there are no other devices using the same IP address
Verify the sensor subnet is valid
Verify the sensor can be successfully pinged
Verify the network
firewall settings support connection to the
sensor