176.10 Value analog input 3
FLOAT -25 to +25
Sensor 1 Pressure actual value from add-on module SVP.
Scaling:
Voltage input: 1 V = 1,0
Current input: 1 mA = 1,0
176.11 Value analog input 4
FLOAT -25 to +25
Sensor 2 Pressure actual value from add-on module SVP.
Scaling:
Voltage input: 1 V = 1,0
Current input: 1 mA = 1,0
176.16 Value analog output 1
FLOAT -11 V to +11 V
Analog output 1 of add-on module SVP is hard-linked to pressure actual value
(ZP177.119–).
Scaling: 1073741824 Inc = Maximum pressure (ZP177.6–)
176.17 Value analog output 2
FLOAT -11 V to +11 V
Analog output 2 of add-on module SVP is hard-linked to speed actual value (P18.22).
Scaling: 1073741824 Inc = Maximum speed of drive (P110.13)
176.18 Value analog output 3
FLOAT -11 V to +11 V
Analog output 3 of add-on module SVP is hard-linked to Iq actual value (P47.3).
Scaling: 1073741824 Inc = Maximum drive current (P119.6)