Parameters
Application handbook Servo pump function V1 for BM5000
Document No.: 5.17002.02
67
of 76
6
177.175 P actual value sensor 1
INT -32768 to +32767
Pressure actual value of Sensor 1.
Hardware-connection to input 1 of standard analog IO (connector X6) or input 3 of add-
on module SVP.
The active sensor for pressure control can be selected via bit 7 of control word SP 1
(ZP177.3).
Scaling: 32767 Inc = ZP177.6 or ZP177.7
177.176 P actual value sensor 2
-32768 to +32767
Pressure actual value of Sensor 2.
Hardware-connection to input 2 of standard analog IO (connector X6) or input 4 of add-
on module SVP.
The active sensor for pressure control can be selected via bit 7 of control word SP 1
(ZP177.3).
Scaling: 32767 Inc = ZP177.6 or ZP177.7
177.191 Actuating variable 1
DS-support DINT 0 to 32767
Control difference of the adaption point 1.
Scaling: 32767 Inc = ZP177.6 or ZP177.7
177.192 Actuating variable 2
DS-support DINT 0 to 32767
Control difference of the adaption point 1.
Scaling: 32767 Inc = ZP177.6 or ZP177.7
177.193 Actuating variable 3
DS-support DINT 0 to 32767
Control difference of the adaption point 1.
Scaling: 32767 Inc = ZP177.6 or ZP177.7