CT-600-2 101
No. Alarm / warning
description
Related
function
Possible causes
202 Dev.check: ctrl source 2.28 Module not setup correctly for modbus (serial)
communication
203 Dev.check: ctrl timeout fct 2.28 Module not setup correctly for modbus (serial)
communication
204 Dev.check: ctrl timeout time 2.28 Module not setup correctly for modbus (serial)
communication
205 Dev.check: refrigerant 2.28 Module not setup correctly regarding selected refrigerant
206 Dev.check: oem-type 2.28
207 Dev.check: sys voltage 2.28 Module system voltage not aligned with parameter for
system voltage
208 Dev.check: eco enable 2.28
209 Dev.check: comp. Type 2.28 Module compressor type not aligned with parameter for
compressor type
210 Dev.check: soft. Release 2.28 Module software release not aligned with parameter for
software release
211 Dev.check: modbus scheme 2.28 Module modbus scheme not aligned with expeced scheme
220 IQ-Module disabled 2.28 Module disabled in Service\Communication Setup
221 IQ-Module operation
disabled
2.28 Module operation disabled
222 Compressor start disabled 2.28 Any active compressor alarm dissables start
223 Start and run signal
opposite
2.28 Ramp time VSD too high
224 Unspecified alarm 2.28