104 CT-600-2
15.3 List of data signals and addresses on Modbus TCP/IP
Address Signal
No.
Signal name Unit
%MW40032 - %MW40033 0 Number of enabled compressors
%MW40034 - %MW40035 1 Number of running compressors
%MW40036 - %MW40037 2 Number of compressors with fault
%MW40038 - %MW40039 3 Number of compressors with eco valve open
%MW40040 - %MW40041 4 Module capacity setpoint %
%MW40042 - %MW40043 5 Module actual capacity %
%MW40044 - %MW40045 6 Suction temperature °C
%MW40046 - %MW40047 7 Suction pressure bara
%MW40048 - %MW40049 8 Suction superheat °C
%MW40050 - %MW40051 9 Discharge temperature °C
%MW40052 - %MW40053 10 Discharge pressure bara
%MW40054 - %MW40055 11 Process temperature °C
%MW40056 - %MW40057 12 Total current A
%MW40058 - %MW40059 13 Min. module capacity setpoint for start %
%MW40060 - %MW40061 14 Module status (0 =stop, 1=manual, 2=auto,
3=remote, 4=service, 5=remote ind.)
...
... ... ...
%MW40072 - %MW40073 20 Oil pressure before filter bara
%MW40074 - %MW40075 21 Oil pressure after filter bara
%MW40076 - %MW40077 22 Oil temperature °C
%MW40078 - %MW40079 23 Oil separator temperature °C
%MW40080 - %MW40081 24 Status oil heaters
%MW40082 - %MW40083 25 Status oil system running
%MW40084 - %MW40085 26 Status coalescer oil return
%MW40086 - %MW40087 27 Status booster oil pump
%MW40088 - %MW40089 28 Switch oil separator low level
%MW40090 - %MW40091 29 Switch oil separator high level
%MW40092 - %MW40093 30 Switch coalescer oil level
...
... ... ...
%MW40112 - %MW40113 40 Economizer suction temperature °C
%MW40114 - %MW40115 41 Economizer suction pressure bara
%MW40116 - %MW40117 42 Economizer suction superheat °C
%MW40118 - %MW40119 43 Economizer liquid out temperature °C
%MW40120 - %MW40121 44 Economizer liquid level
%MW40122 - %MW40123 45 Status economizer liquid supply