EasyManua.ls Logo

Bitzer ACP Link - Overview of Timers in ACP LINK

Bitzer ACP Link
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CT-600-2 85
No. Description Param. page
on HMI
Default
value
Default
unit
136 PID inner window I-part hot water PID 2- 4 0 °C
137 PID outer window I-part hot water PID 2- 4 0 °C
138 Enable/disable economizer Economizer OFF
139 Eco superheat low warning Economizer 0.5 °C
140 Eco superheat low alarm Economizer 0.0 °C
141 Eco superheat high warning Economizer 20 °C
142 Eco superheat high alarm Economizer 50 °C
13.2 Overview of timers in ACP LINK
No. Description Param. page
on HMI
Default
value (s)
1 Suction press. low warning time Timer 1 3600
2 Suction press. high warning time Timer 1 3600
3 Discharge press. high warning time Timer 1 3600
4 Press. ratio high warning time Timer 1 3600
5 Press. diff. low warning time Timer 1 3600
6 Lubric. press. low warning time Timer 1 3600
7 Suct. superheat low time to alarm Timer 1 30
8 Oil sep. level low warning time Timer 1 10800
9 Oil sep. coal. high time to warning Timer 1 600
10 Oil sep. load high warning time Timer 1 3600
11 Total current high warning time Timer 2 3600
12 Process temp. low warning time Timer 2 3600
13 Pump motor feedback low time Timer 2 20
14 Capacity limiter time step Timer 2 30
15 Coal. oil ret. valve open time Timer 2 30
16 Pump oil pressure low time Timer 2 60
17 Eco liq. level high warning time Timer 2 30
18 Eco superheat low time to alarm Timer 2 30
19 Eco oil level high time to warning Timer 2 600
20 Eco oil ret. valve open time Timer 2 30
21 Eco oil ret. start delay time Timer 3 60
22 Alarm delay low press. diff. Timer 3 5
23 Alarm delay low lubric. press. Timer 3 5
24 Alarm delay low discharge press. Timer 3 5
25 Alarm delay low oil sys. temp. Timer 3 300

Table of Contents

Related product manuals