CT-600-2 85
No. Description Param. page
on HMI
Default
value
Default
unit
136 PID inner window I-part hot water PID 2- 4 0 °C
137 PID outer window I-part hot water PID 2- 4 0 °C
138 Enable/disable economizer Economizer OFF
139 Eco superheat low warning Economizer 0.5 °C
140 Eco superheat low alarm Economizer 0.0 °C
141 Eco superheat high warning Economizer 20 °C
142 Eco superheat high alarm Economizer 50 °C
13.2 Overview of timers in ACP LINK
No. Description Param. page
on HMI
Default
value (s)
1 Suction press. low warning time Timer 1 3600
2 Suction press. high warning time Timer 1 3600
3 Discharge press. high warning time Timer 1 3600
4 Press. ratio high warning time Timer 1 3600
5 Press. diff. low warning time Timer 1 3600
6 Lubric. press. low warning time Timer 1 3600
7 Suct. superheat low time to alarm Timer 1 30
8 Oil sep. level low warning time Timer 1 10800
9 Oil sep. coal. high time to warning Timer 1 600
10 Oil sep. load high warning time Timer 1 3600
11 Total current high warning time Timer 2 3600
12 Process temp. low warning time Timer 2 3600
13 Pump motor feedback low time Timer 2 20
14 Capacity limiter time step Timer 2 30
15 Coal. oil ret. valve open time Timer 2 30
16 Pump oil pressure low time Timer 2 60
17 Eco liq. level high warning time Timer 2 30
18 Eco superheat low time to alarm Timer 2 30
19 Eco oil level high time to warning Timer 2 600
20 Eco oil ret. valve open time Timer 2 30
21 Eco oil ret. start delay time Timer 3 60
22 Alarm delay low press. diff. Timer 3 5
23 Alarm delay low lubric. press. Timer 3 5
24 Alarm delay low discharge press. Timer 3 5
25 Alarm delay low oil sys. temp. Timer 3 300