84 CT-600-2
No. Description Param. page
on HMI
Default
value
Default
unit
100 PID TV suction pressure (D) PID 2 - 1 0 s
101 PID TD suction pressure PID 2 - 1 1 s
102 PID setpoint ramp limit suction pressure PID 2 - 1 10.0 min/bar
103 PID deadband suction pressure PID 2 - 1 0.0 bar
104 PID output high limit suction pressure PID 2 - 1 100 %
105 PID output low limit suction pressure PID 2 - 1 -100 %
106 PID inner window I-part suction pressure PID 2 - 1 0.0 bar
107 PID outer window I-part suction pressure PID 2 - 1 0.0 bar
108 PID KP cold brine (P) PID 2 - 2 5.0 %/°C
109 PID TN cold brine (I) PID 2 - 2 60 s
110 PID TV cold brine (D) PID 2 - 2 0 s
111 PID TD cold brine PID 2 - 2 1 s
112 PID setpoint ramp limit cold brine PID 2 - 2 2.0 min/°C
113 PID deadband cold brine PID 2 - 2 0.0 °C
114 PID output high limit cold brine PID 2 - 2 100 %
115 PID output low limit cold brine PID 2 - 2 -100 %
116 PID inner window I-part cold brine PID 2 - 2 0 °C
117 PID outer window I-part cold brine PID 2 - 2 0 °C
118 PID KP discharge pressure (P) PID 2 - 3 20.0 %/bar
119 PID TN discharge pressure (I) PID 2 - 3 30 s
120 PID TV discharge pressure (D) PID 2 - 3 0 s
121 PID TD discharge pressure PID 2 - 3 1 s
122 PID setpoint ramp limit discharge pressure PID 2 - 3 10.0 min/bar
123 PID deadband discharge pressure PID 2 - 3 0.0 bar
124 PID output high limit discharge pressure PID 2 - 3 100 %
125 PID output low limit discharge pressure PID 2 - 3 -100 %
126 PID inner window I-part discharge pressure PID 2 - 3 0.0 bar
127 PID outer window I-part discharge pressure PID 2 - 3 0.0 bar
128 PID KP hot water (P) PID 2- 4 5.0 %/°C
129 PID TN hot water (I) PID 2- 4 60 s
130 PID TV hot water (D) PID 2- 4 0 s
131 PID TD hot water PID 2- 4 1 s
132 PID setpoint ramp limit hot water PID 2- 4 2.0 min/°C
133 PID deadband hot water PID 2- 4 0.0 °C
134 PID output high limit hot water PID 2- 4 100 %
135 PID output low limit hot water PID 2- 4 -100 %