CT-600-2 17
Terminal plan ACP LINK panel
Emergen
cystop
X9
4
Emerg.
stop
Emerg.stopreturn2
Dep.On
customerem.
stopcircuit
Emergencystop
customerelectricalpanel
3 Emerg.stopreturn1
2 Emerg.stopsupply2
1 Emerg.stopsupply1
Modbus,
SupplyM172
X8.3
6 24VDC‐
ForM172andECO
system(optional)
O
3x1.0
(1,2+Gnd)
>6A
M172andCM‐IO‐ECOare
suppliedfromhere
5 24VDC+O
4 Notused
3 RS485+
ModbusRTU
3x0.6
(ModbusRTU
standard)
NOTE:connectmodbusacc.
tosection
2 RS485‐
1
RS485GS
Compressor3
X8.2
6! L Startsignaltocustomer 230/120VAC O BK
!Screwterminalsbehind
connector!
5! L HPSafetyChain 230/120VAC O GR
4
Internallyconnected
Cable:5x1.0
(BN,BL,GR,BK+GND)
Validfrom03/2019
3
2 N
Customersupply 230/120VAC I
BL
>6A
1 L BN
Compressor2
X8.1
6! L Startsignaltocustomer 230/120VAC O BK
!Screwterminalsbehind
connector!
5! L HPSafetyChain 230/120VAC O GR
4
Internallyconnected
Cable:5x1.0
(BN,BL,GR,BK+GND)
Validfrom03/2019
3
2 N
Customersupply 230/120VAC I
BL
>6A
1 L BN
Compressor1
X8.0
6! L Startsignaltocustomer 230/120VAC O BK
!Screwterminalsbehind
connector!
5! L HPSafetyChain 230/120VAC O GR
4
Internallyconnected
Cable:5x1.0
(BN,BL,GR,BK+GND)
Validfrom03/2019
3
2 N
Customersupply 230/120VAC I
BL
>6A
1 L BN
Oil
res.
X5.2
2 N
Tocustomer
(Optionaloilreservoir)
O
Dep.on
customer
NOTE:functionalitynot
implementedyet.
1 L
Eco
X5.1
4 N
Economizersupply 230/120VAC O
3x1.0
(1,2+Gnd)
NOTE:IfusingECO,connect
modbusacc.tosection
3 L
Oil
sep
2
Internallyconnected 230/120VAC O
3x1.0
(1,2+Gnd)
1
Customermain
supply
X5.0
6 PE
Customersupply 230/120VAC I
3x1.5
(1,2+Gnd)
10
5 24VDC‐
4 24VDC+
3 PE
Customersupply 24VDC I
3x1.5
(1,2+Gnd)
16
2 N
1 L
Designation
Row
Terminal
Connection
Description
Voltage
Direction
Cable
Fusemin.
rating[A]
Note