168 Brocade MLXe Series Hardware Installation Guide
53-1003030-01
Managing the cooling system
5
Fan Speed Low: -1 - 50
Fan Speed Med: 46 - 55
Fan Speed Med-Hi: 51 - 60
Fan Speed Hi: 56 - 95
state = 0 (FAN_STATE_LOW)
max_ts_shut_off_count = 1
shut_off_count = 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
=== Thermal Sensor Control Block (THERMAL_SENSOR_TEST_RULE_LP_XPP) ===
Fan Speed Low: -1 - 50
Fan Speed Med: 45 - 65
Fan Speed Med-Hi: 60 - 75
Fan Speed Hi: 70 - 113
state = 1 (FAN_STATE_MED)
max_ts_shut_off_count = 1
shut_off_count = 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
=== Thermal Sensor Control Block (THERMAL_SENSOR_TEST_RULE_STANDBY_MP) ===
Fan Speed Low: -1 - 60
Fan Speed Med: 57 - 70
Fan Speed Med-Hi: 67 - 80
Fan Speed Hi: 77 - 85
state = 0 (FAN_STATE_LOW)
max_ts_shut_off_count = 1
shut_off_count = 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
=== Thermal Sensor Control Block (THERMAL_SENSOR_TEST_RULE_MP_CPU) ===
Fan Speed Low: -1 - 60
Fan Speed Med: 57 - 70
Fan Speed Med-Hi: 67 - 80
Fan Speed Hi: 77 - 95
state = 1 (FAN_STATE_MED)
max_ts_shut_off_count = 1
shut_off_count = 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
=== Thermal Sensor Control Block (THERMAL_SENSOR_TEST_RULE_STANDBY_MP_CPU) ===
Fan Speed Low: -1 - 60
Fan Speed Med: 57 - 70
Fan Speed Med-Hi: 67 - 80
Fan Speed Hi: 77 - 95
state = 0 (FAN_STATE_LOW)
max_ts_shut_off_count = 1
shut_off_count = 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Syntax: show fan-threshold
The output displays the following information.
TABLE 35 Temperature threshold information for modules and fan speeds
This field... Displays...
Thermal Sensor Control Block
(THERMAL_SENSOR_TEST_RULE_m
odule)
The temperature threshold information for the various modules. The
module parameter indicates the following:
MP – The active management module
STANDBY_MP – The standby management module
SNM – The switch fabric module
LP – An interface module
Fan Speed Low or Med or Med-Hi or
Hi
The current setting of the low and high temperature thresholds for the low,
medium, medium-high, and high fan speeds.
NOTE: As indicated in Table 36, the low fan speed for each module does
not have a default low temperature threshold value, nor can you
configure this value. The “-1” value that appears in the Fan Speed
Low field for each module is a Brocade internal value only.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Brocade Communications Systems MLXe Series and is the answer not in the manual?

Brocade Communications Systems MLXe Series Specifications

General IconGeneral
BrandBrocade Communications Systems
ModelMLXe Series
CategoryControl Unit
LanguageEnglish

Related product manuals