Installation and Operation Manual
X-VA-MT3809G-MT3810G-eng
Part Number: 541B182AAG
July, 2018
Models MT3809G & MT3810G
Design Features
• 4-20 mA analog output for owrate
• Bell-202 modulated HART digital communication over the 4-20 mA signal
• Current loop powered 2-wire connection
• User selectable 0% and 100% analog output ranges with optional
smoothing
• Flexible (mix & match) units of measure for owrates, totals,
temperatures, densities, etc.
• Two ow totalizers: Resettable and inventory totalization
• User congurable, scalable pulse output for various engineering units
• Hi- and Lo-ow alarm output
Description
The 4-20 mA with HART transmitter is a compact microprocessor device
designed to interface directly with the Model MT3809. This transmitter
includes a Hi- and Lo alarm switch output and a pulse output.
The HART digital communication signals are superimposed on top of the
4-20 mA signal, allowing communication of more than just the process
variable.
The transmitter is HART-programmable or for numerous variables such as
ow rate, totalization, calibration factors, and high-low alarm parameters.
It is programmable with easy-to-use hand held congurators. Prior to
shipment, commonly used default values are programmed by Brooks to
ensure ease of operation and quick startup. However, parameters may be
reprogrammed by the user if needed. Flow rate information may be viewed
locally at the meter scale, LCD display or displayed remotely.
Powersupplyvoltage 21to30Vdc:(2Ͳwirecurrentlooptransmitter)
Loopcurrent/currentconsumption
range
3.8to22.0mA.
Opencollectoralarmoutput
Opticallyisolatedoutputsassignabletoalarms.
•Max.offͲstatevoltage:30Vdc
•Max.offͲstatecurrent:0,05mA
•Max.onͲstatevoltage:1.2Vdc
•Max.onͲstatecurrent:20mA
Opticallyisolated.Scalabletoavarietyofengineeringunitsystems(pulsesperliter,gallons,
etc.).
•Range:1Hzto1kHz
•Max.offͲstatevoltage:30Vdc
•Max.offͲstatecurrent:0.05mA
•Max.onͲstatevoltage:1.2Vdc
•Max.onͲstatecurrent:20mA
TemperatureSpecification SeeTemperatureCutͲoff Table
M20x1,5accordingtoISO(1/2"NPT,3/4”NPT(F)orcableglandoptional)
•Brass/Nickelplatedcableglandcablediameterrange8Ͳ11mm(Aluminumhousing)
•Stainlesssteelcableglandcablediameterrange7Ͳ10.5mm(SShousing)
Linearity Lessthan1%atmax.current.
Temperatureinfluence Lessthan0.04%per°C.
Voltageinfluence Lessthan0.002%/Vdc.
Loadresistanceinfluence ±0.1%fullscale.
HARTRevision HARTͲ7
HiͲandLoͲalarmoutputs
PulseOutput
ElectricalConnector
Table 1-7 4-20 mA with HART Transmitter Description Table
1-7-1 Current Loop 4-20 mA with HART Transmitter, with Alarms, Display and Pulse Output