1-7-2 Foundation Fieldbus Transmitter, with Alarms and Pulse Output
Design Features
• Foundation
TM
Fieldbus digital communication network interface
• Ease of wiring and installation with a single 2-wire bus connection
• Powered over 2-wire Foundation
TM
Fieldbus connection
• Flexible (mix & match) units of measure for owrates, totals,
temperatures, densities, etc.
• Two ow totalizers: Resettable and inventory totalization
• User congurable, scalable pulse output for various engineering units
• Hi- and Lo-ow alarm output
Description
The Foundation
TM
Fieldbus transmitter is a compact microprocessor device
designed to interface directly with the Model MT3809.
The transmitter communicates over the 2-wire network per the
international Foundation
TM
Fieldbus standard for access to numerous
variables such as ow rate, totalization, calibration factors, and high-low
alarm parameters.
Table 1-8 Foundation Fieldbus Transmitter Description Table
Powersupplyvoltage 9Ͳ32Vdc
Powersupplyprotection Protectedagainstreversepolarity
Currentconsumption 12mA
Entiretransmitterispoweredfrom2Ͳwirebus
HiͲandLoͲalarmoutputs Opencollectoralarmoutput
Opticallyisolatedoutputsassignabletoalarms.
•Max.offͲstatevoltage:30Vdc
•Max.offͲstatecurrent:0,05mA
•Max.onͲstatevoltage:1.2Vdc
•Max.onͲstatecurrent:20mA
PulseOutput
Opticallyisolated.Scalabletoavarietyofengineeringunitsystems(pulsesperliter,gallons,
etc.).
•Range:1Hzto1kHz
•Max.offͲstatevoltage:30Vdc
•Max.offͲstatecurrent:0.05mA
•Max.onͲstatevoltage:1.2Vdc
•Max.onͲstatecurrent:20mA
TemperatureSpecification SeeTemperatureCutͲoffTable
ElectricalConnector M20x1,5accordingtoISO(1/2"NPT,3/4”NPT(F)orcableglandoptional)
•Brass/Nickelplatedcableglandcablediameterrange8Ͳ11mm(Aluminumhousing)
•Stainlesssteelcableglandcablediameterrange7Ͳ10.5mm(SShousing)
Linearity Lessthan1%
TemperatureInfluence Lessthan0.04%per°C
Voltageinfluence Lessthan0.002%/Vdc
FOUNDATIONFieldbusRevision ITK6