Entering system settings (Service menu – Settings)
Logamatic EMS RC35 user interface - Subject to technical modifications.30
6
Set temperature for
frost protection.
–4 °F – +50 °F
(–20 °C – +10 °C)
41 °F (5 °C) Refers to outdoor temperature
(Æ page 35).
At what outdoor
temp. should the
setback be
canceled?
OFF,
–22 °F – 50 °F
(–30 °C – +10 °C)
OFF
Confirm activating
DHW priority.
yes, no no
Mixing valve
Is a mixing valve
installed?
yes, no yes Can only be set for heating
zones 2 and up.
What is the run
time of the mixing
valve?
10 – 600 seconds 120 seconds
What increase
should be used for
the boiler?
F 3F
(0 °C – 20 °C)
10 °F (5 °C)
Drying floor radiant slab
Confirm running a
slab drying cycle.
yes, no no Can only be set if radiant floor
heating has been entered as the
heating system. DHW heating is
disabled while slab is drying.
Set the frequency
for raising the
supply
temperature.
every day, every 2nd
day to every 5th day
daily
Set the supply
temperature
increase.
F 7F
(0 K – 40 K)
F (C)
Set the maximum
supply
temperature.
77 °F – 140 °F
(25 °C – 60 °C)
113 °F (45 °C)
For how many days
should max. supply
temp. be
maintained?
0 – 20 days 4 days
Menu item Input range
Factory
setting Other information
Tab. 12 Navigator for Service menu SETTINGS\HTG. ZONE 1