Camus ProtoNode Startup
G id
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web:
www.protocessor.com
Tel: (408) 964-4444 Fax: (408) 964-4425 email: support@protocessor.com
Camus ProtoNode Startup
G id
Page 59 of 87
Outdoor temperature
R
00AA
0170
AI
41
AI
nvoXOutdoorTmp
SNVT_temp_p
40 200
o
F
1
Burner switch
R/W
00CB
0203
AV
47
AO
nvi/nvoXBrnSwitch
SNVT_count_f
Used to enable/disable burner
control.
0 = Off
1 = On
NOTE: Writing to this point will
result in an alert appearing on screen
CH enable
R/W
00D0
0208
AV
48
AO
nvi/nvoXEnable
N/A
0 = Disable Central Heating
1 = Enable Central Heating
CH setpoint
R/W
00D3
0211
AV
49
AO
nvi/nvoXCHSP
SNVT_temp_p
40 200
o
F
1
DHW Enable
R/W
01C1
0448
AV
54
AO
nvi/nvoXDHWEnable
SNVT_count_f
0 = DHW Disabled
1 = DHW Enabled
DHW Setpoint
R/W
01C5
0453
AV
55
AO
nvi/nvoXDHWSP
SNVT_temp_p
40 200
o
F
1
Lead Lag Master Enable
R/w
0221
0545
AV
64
AO
nvoXLdLgMstrEnbl
SNVT_count_f
0 = Not a Lead/Lag master
1 = Lead/Lag master
Lead Lag setpoint
R/W
0222
0546
AV
65
AO
nvi/nvoXLdLgSetpoint
SNVT_temp_p
40 200
o
F
1
Burner cycle count
R
0080-
0081
0128-
0129
AV
89
AO
N/A
N/A
0-999,999
Burner run time
R
0082-
0083
0130-
0131
AV
90
AO
N/A
N/A
0-999,999 hours
CH pump cycle count
R
0084-
0085
0132-
0133
AV
91
AO
nvi/nvoXCHPmpCycCnt
SNVT_count_f
0-999,999
Lead Boiler Address
R
0321
0801
AI
97
AI
nvoXLdBlrAddr
SNVT_count_f
Modbus address of the first boiler
that will be or was added to service
Lead Lag demand (slave must be
available for firing)
Lead Lag Operation
Switch
R/W
022B
0555
BV
104
DO
nvi/nvoXLdLgOpSwitch
SNVT_switch
To enable/disable the Lead Lag
boiler plant
Active System Setpoint
R
001D
0029
AI
108
AI
nvoXActSysSP
SNVT_count_
p
40 200
o
F
1
Modulation Output
R
00C0
0192
AI
105
AI
nvoXModOutput
SNVT_count_f
0 = Fan PWM
1 = 0-10Vdc
2 = 4-20mA
Max Firing Rate
R
00C1
0193
AI
106
AI
nvoXMaxFirRate
SNVT_count_f
(%
2
or RPM
3
)
Min Firing Rate
R
00C3
0195
AI
107
AI
nvoXMinFirRate
SNVT_count_f
(%
2
or RPM
3
)