Illegal Modbus write was attempted
Modbus write attempt was rejected (NOT ALLOWED)
Illegal Modbus read was attempted
Safety processor brown-out reset occurred
Application processor watchdog reset occurred
Application processor brown-out reset occurred
Safety processor watchdog reset occurred
Alarm was reset by the user at the control
Burner control firing rate was > absolute max rate
Burner control firing rate was < absolute min rate
Burner control firing rate was invalid, % vs. RPM
Burner control was firing with no fan request
Burner control rate (nonfiring) was > absolute max rate
Burner control rate (nonfiring) was < absolute min rate
Burner control rate (nonfiring) was absent
Burner control rate (nonfiring) was invalid, % vs. RPM
Fan off cycle rate was invalid, % vs. RPM
Setpoint was overridden due to sensor fault
Modulation was overridden due to sensor fault
No demand source was set due to demand priority conflicts
CH 4-20mA signal was invalid
Absolute max fan speed was out of range
Absolute min fan speed was out of range
Fan gain down was invalid
Fan minimum duty cycle was invalid
Fan pulses per revolution was invalid
Fan PWM frequency was invalid
Lead Lag CH 4-20mA water temperature setting was invalid
No Lead Lag add stage error threshold was configured
No Lead Lag add stage detection time was configured
No Lead Lag drop stage error threshold was configured
No Lead Lag drop stage detection time was configured
Lead Lag all boiler off threshold was invalid
Modulation output type was invalid
Firing rate control parameter was invalid
Forced rate was out of range vs. min/max modulation
Forced rate was invalid, % vs. RPM
Slow start ramp value was invalid
Slow start degrees value was invalid
Slow start was ended due to outlet sensor fault
Slow start was end due to reference setpoint fault
CH max modulation rate was invalid, % vs. RPM
CH max modulation rate was > absolute max rate
CH modulation range (max minus min) was too small (< 4% or 40 RPM)
DHW max modulation rate was invalid, % vs. RPM
DHW max modulation rate was > absolute max rate
DHW modulation range (max minus min) was too small (< 4% or 40 RPM)
Min modulation rate was < absolute min rate
Min modulation rate was invalid, % vs. RPM
Manual rate was invalid, % vs. RPM