Troubleshooting
164
Capron - 3141417 - 03/20 - EHG-0021-02EN
15
Fault Cause Remedy
Battery charge through
solar module not working
Electrical connection to
solar module interrupted
Check plug connectors and
cables
Fuse is defective Replace fuse on the trans-
former/rectifier
Solar charge regulator
defective
Contact customer service
Living area battery over-
loaded ("hot")
Battery selection switch
set wrongly
Move position of battery se-
lection switch
Defective load sensor or
relay
Pull out the jumbo flat fuse
on the living area battery,
then contact customer ser-
vice
15.3 Gas system
In case of a defect of the gas system (gas odour, high gas consump-
tion) there is danger of explosion! Close regulator tap on the gas bot-
tle immediately. Open doors and windows and ventilate well.
If the gas system is defective: Do not smoke; do not ignite any open
flames, and do not operate electric switches (light switches etc.).
Check the tightness of gas-conducting parts and lines with leakage
search spray. Do not check with an open flame.
Have the defective gas system repaired by an authorised specialist
workshop.
Fault Cause Remedy
No gas Gas bottle is empty Change gas bottle
Gas isolator tap closed Open the gas isolator tap
Regulator tap on the gas
bottle is closed
Open regulator tap on the
gas bottle
External temperature is
too low (-42 °C for pro-
pane gas, 0 °C for butane
gas)
Wait for higher external
temperatures
Built-in appliance is defec-
tive
Contact customer service