Model TANK Fire Suppression Extinguishing System
Installation, Operation, and Maintenance Manual
TANK Fire Suppression Extinguishing System Typical Hood End Cabinet Installation
RECEIVING AND INSPECTION
Check for any signs of damage upon receipt, and if found, report it immediately to the carrier.
Check that all items are accounted for and free of damage.
WARNING!
The TANK Fire Suppression extinguishing system unit is to be installed, inspected, recharged
and maintained in accordance with NFPA 17A, NFPA 96, and the National Fire Code of Canada
as applicable.
Installation and maintenance of the TANK Fire Suppression extinguishing system must be
performed in accordance with this manual by a factory trained distributor. Improper installation
poses serious risk of injury due to electric shock and other potential hazards. Read this manual
thoroughly before installing or servicing this equipment. ALWAYS disconnect power prior to
working on equipment.
Save these instructions. This document is the property of the owner of this equipment and is required
for future maintenance. Leave this document with the owner when installation or service is complete.
Part No. A0029342
January 2024 Rev 24

Table of Contents

Questions and Answers

  • A
    Anthony ThomasSep 12, 2025
    What does 7 flashes mean on CaptiveAire TANK Fire Extinguisher?
    • P
      Paula VillarrealSep 12, 2025
      If the system flashes seven times, check the wiring to all the manual actuation devices (push/pull stations) and fire sensors for shorts to ground, replace as needed. Refer to “Supervised Loop Electrical Details” on page 46.
  • D
    Dennis CastilloSep 10, 2025
    What does 4 flashes mean on CaptiveAire Fire Extinguisher?
    • A
      Alicia WalterSep 12, 2025
      If the system flashes four times, check supervised Pressure Regulating Valves (optional) and Pressure Switches (optional).
  • M
    Michelle WilliamsSep 9, 2025
    What does 3 flashes mean on CaptiveAire TANK?
    • D
      Donna RobertsSep 9, 2025
      If the system flashes three times, check the solenoid and wiring to the solenoid, replacing as needed.
  • J
    Jennifer GraySep 8, 2025
    What does 2 flashes mean on CaptiveAire Fire Extinguisher?
    • B
      Bryan PayneSep 8, 2025
      If the system flashes twice, check the solenoid and wiring to the solenoid, replacing as needed.
  • T
    Terry CoxAug 23, 2025
    What to do if the Fire System Activated Light is on in my CaptiveAire TANK Fire Extinguisher?
    • R
      Rachel PattersonAug 23, 2025
      If the Fire System Activated Light is on, this indicates that the fire system has been activated. Verify that the fire is out, and then reset the fire system.
  • A
    Anna RossSep 6, 2025
    What causes problems with Release Solenoid in CaptiveAire Fire Extinguisher?
    • J
      Joshua BrownSep 6, 2025
      Problems with the release solenoid can stem from: * Incorrect solenoid wiring: Check RS to N1D when: * Wire removed from RS terminal = 15.5DC V +/- 2V * RS terminal wired, connector removed = 6.5DC V +/- 2V * RS terminal wired, connector installed = 0.2-0.4DC V * The connector is not secured to the solenoid: Verify the connector is secured to the valve.
  • J
    Jennifer ForbesSep 4, 2025
    What does Ground Fault mean in CaptiveAire TANK Fire Extinguisher?
    • A
      Andrew RamirezSep 4, 2025
      A Ground Fault can be caused by: * Terminals 22 or 23 shorted to chassis ground. *24V DC PS-02 (DC-) Wiring or Components: Locate and repair shorted wiring between the 22-23 supervised loop and ground. * Terminals 21 or 24 shorted to chassis ground. **24V DC PS-02 (DC+) Wiring or Components: Locate and repair shorted wiring between the 21-24 supervised loop and ground. * Interlock Network Issue: Check battery voltage and supervised loop wiring with other packages that are interlocked in the network.
  • I
    ireynoldsSep 3, 2025
    What causes Supervised Loop Fault in CaptiveAire TANK Fire Extinguisher?
    • J
      johnstonamberSep 4, 2025
      A Supervised Loop Fault can occur due to several reasons: * Open Supervised Loop between Terminals 21 and 24: Locate and repair faulty wiring in the 21-24 supervised loop. * Open Supervised Loop between Terminals 22 and 23: Locate and repair faulty wiring in the 22-23 supervised loop. * Open Supervised Loop Push- Station (Terminals 101 and 104): Locate and repair faulty wiring in the 101-104 supervised loop. * Open Supervised Loop Push- Station (Terminals 102 and 103): Locate and repair faulty wiring in the 102-103 supervised loop.
  • A
    Aaron TurnerSep 2, 2025
    What to do if battery voltage is low in CaptiveAire TANK Fire Extinguisher?
    • E
      esimonSep 2, 2025
      If the battery voltage is low, it could be due to: 1. A faulty battery or power supply (PS-02). Verify there is 12V DC to each battery connection. Locate and repair any faulty wiring in the circuit. Replace the batteries. 2. An interlock network issue. Check the battery voltage and supervised loop wiring with other packages that are interlocked in the network.
  • M
    Marcus HaleSep 1, 2025
    What to do if gas valve does not close in CaptiveAire Fire Extinguisher?
    • N
      Nicholas ContrerasSep 1, 2025
      If the gas valve doesn't close, it's likely due to debris on the gas valve seal. Fully clean the gas valve and strainer to resolve this.

Summary

Warranty

System Overview

Provides a general description of the fire suppression system's function and components.

Components

Cylinder Tank Assembly

Cylinder Tank and Actuator Bracket

Primary Actuator Kit (PAK)

Secondary Valve Actuator (SVA) and Hose

Supervisory Pressure Switch

Gas Shut-Off Valves

Firestat (Heat) Detector

Installation

Cylinder Tanks

Explains the typical installation and mounting of agent storage cylinders within the cabinet.

Primary and Secondary Actuator Installation

Secondary Valve Actuator (SVA)

Supervisory Pressure Switch Installation

Duct and Plenum Protection

Appliance Protection

Upright Broiler;Salamander Protection

Appliance with Shelf

Wok Protection

Large Wok Protection

Appliance with Upright Obstruction

Appliance with Overhead Salamander

Pizza Ovens

Agent Distribution Piping

Cylinder Nozzle and Piping Parameters

Firestat Installation Details

Firestat Components

Hood Riser Sensor Replacement

Fire Protection Manual Actuation Device

Fire Protection System Printed Circuit Board

Electrical

Fire Protection System Supervised Loops

Supervised Loop Electrical Details

PCU Fire System

PCU Fire System Nozzles

Operation

Test Mode Overview

Reset Overview

Battery Backup

Fire Protection System Firestat

Troubleshooting

CORE Board Faults

Appliance Shutdown in Fault Conditions

Supervised Loop Wiring Troubleshooting

DIP Switch Settings

Start-Up;Inspection Test Procedure

Connecting Service Test Kit

Balloon Test Procedure

Firestat Test Procedure

Re-arming System

Leakage Testing

Maintenance

Every Six Months (Factory Trained Distributor)

Conditional Maintenance

Replacing A Primary Actuation Kit

Step-by-step guide for replacing a faulty primary actuator kit.

Replacing A Secondary Valve Actuator

Instructions for replacing a malfunctioning secondary valve actuator.

Adding Nitrogen to Tank(s)

Post-Discharge Maintenance

Flushing the Distribution Pipe Network

Flushing Procedure with Spare;Test Cylinder

Details flushing the network using a spare or test cylinder.

Flushing Procedure with an External Water Supply

Cylinder Tank Maintenance

Removing a Cylinder Tank (Empty or Storage)

Instructions for safely removing cylinders from the system for maintenance or storage.

Install New Cylinder Tank(s)

Depressurizing a Cylinder Tank

Mobile Kitchen;Seasonal Shutdown

Start-Up and Maintenance Documentation

CaptiveAire TANK Specifications

General IconGeneral
Agent TypeWet Chemical
ApplicationRestaurant, Commercial Kitchen
Extinguishing AgentWet Chemical
Operating Pressure100 psi
Discharge Time40 seconds
Weight22 lbs
MaterialSteel Cylinder
StandardsANSI/UL 8, ULC S554, NFPA 10