8200-M585-O1 Rev D 210 Installation & Technical 37
SETUP AND CALIBRATION, CONT.
A - d (A - d?) – Analog to Digital Filtering
SErSCL – (REMOTE INDICATOR SETUP)
If the indicator is to function as a remote indicator, press the YES key at the SErSCL prompt. If
not then press the NO key at the prompt.
IMPORTANT! If a 200, 205, 210 or 215 indicator is to be used as the LOCAL and
as the REMOTE, then both indicators MUST have Rev 2.6.3 or greater software
installed.
If a combination of 200, 205, 210 or 215 and a 225 indicator are to be used in a
LOCAL/REMOTE configuration, then the remote 200, 205, 210 or 215 indicator
MUST have Rev 2.6.1 or greater software installed, and the 225 indicator MUST
have Rev 1.0.K or greater software installed.
LrP= (Local/Remote Port)
NOTE: This will only be displayed if
SERSCL was set to YES
Press the ENTER key to show the current value. If the setting displayed is acceptable, press
the ENTER key again to save it. Otherwise, using the numeric keys enter the new setting
and then press the ENTER key to save it. Allowable values are: 0, 1, 2 or 3 (for port 0
through port 3) and 4 for the optional 2xx-RS232 card (if installed).
Refer to the LOCAL/REMOTE SETUP section of this manual for more information and
interconnect wiring diagrams.
dFLt= (Digital Filtering)
With A - d (A - d?) displayed, press the ENTER key. The display will change to dFLt=.
Press the ENTER key to show the current value.
If the setting displayed is acceptable, press the ENTER key to save it. Otherwise, using the
numeric keys enter the new setting, then press the ENTER key to save it. Allowable values
are: 0, 1, 2 or 3. Note, that if you select 3 (Custom Filtering) two additional prompts will be
displayed.
dFLt=
0 Disabled – NO Filtering
1 MINIMAL FILTERING (sample rate = 2)
2 MODERATE FILTERING (sample rate = 1)
3 CUSTOM FILTERING
NOTE: The prompts, F= (Filter Level), h= (High Frequency Filter Value) and b= (Break
Range) will only
be displayed if you selected 3 (Custom Filtering) for the dFLt= (Digital
Filtering) prompt.
F= (Filter Level)
Press the ENTER key to show the current setting for the filter level. The filter level is a number
from 0 to 99 that corresponds to the level of filtering with 99 being the greatest filtering and 1
the least.
To accept the value displayed, press the ENTER key, otherwise, use the numeric keys to enter
a new value then press the ENTER key to save it. Note that entry of a 0 disables this feature.