Models for indoor installation:
INDOOR models UG045 UG090 UG150 UG180 UG300
rated supply voltage (Vac) 230 V 50 Hz (ver. UG***HD004) / 115V 60 Hz(ver. UG***HD1104)
steam connection (Ø mm) 2x40 2x40 1x80 4x40 2x80
steam outlet pressure limits (Pa) 0-2000 (0-0.30 PSI)
feedwater
connection 3/4”
temperature limits °C (°F) 1-40 (33.8-104)
pressure limits (MPa) 0.1-0.8 (1-8 bars) (14.5-166 PSI)
fill water instant flow-rate (l/min) 18 (4.76 US gall/min)
drain water
connection ø mm (in) 50 (1.97)
typical temperature °C (°F) ≤100 (212)
drain water instant flow-rate (l/min) 32 (6.60 gall/min)
operating conditions 1T40°C (33T104°F); 10-90% rH non cond.
storage conditions -10T70°C (14T158°F), 5-95% rH
protection rating IP20
auxiliary voltage / frequency (V- Hz) 24 / 50-60
instant steam production (kg/h / lbs/h) (1) 45 (100) 90 (200) 150 (330) 180 (400) 300 (660)
power consumption at rated voltage (W) 180 250 260 385 400
Tab.16.a
(1) average steam production is affected by factors, such as: ambient temperature, water quality, steam
distribution system.
Models for outdoor installation:
OUTDOOR models UG045 UG090 UG150 UG180 UG300 UG450
rated supply voltage (Vac) 230 V50 Hz (ver. UG***YD004) / 115 V 60 Hz (version UG***Y1104)
steam connection (Ø mm) 2x40 2x40 1x80 4x40 2x80 3x80
steam outlet pressure limits (Pa) 0-2000 (0-0.30 PSI)
feedwater
connection 3/4”
temperature limits °C (°F) -20 to + 45 (33.8-113) with heaters
pressure limits (MPa) 0.1-0.8 (1-8 bars) (14.5-166 PSI)
fill water instant flow-rate (l/min) 18 (4.76 US gall/min)
drain water
connection ø mm (in) 50 (1.97)
typical temperature °C (°F) ≤100 (212)
drain water instant flow-rate (l/min) 32 (6.60 gall/min)
operating conditions 1T45°C (33T104°F); 10-90% rH non cond.
storage conditions -10T70°C (14T158°F), 5-95% rH
protection rating outdoor IAS 12-94
auxiliary voltage / frequency (V- Hz) 24 / 50-60
instant steam production (kg/h / lbs/h) (1) 45 (100) 90 (200) 150 (330) 180 (400) 300 (660) 450 (1000)
power consumption at rated voltage (W) 180 250 260 385 400 660
Tab.16.b
(1) average steam production is affected by factors, such as: ambient temperature, water quality, steam
distribution system.
controller specifications: