EasyManua.ls Logo

Carel gaSteam UG045 - Menu E. Settings - D.master;Slave

Carel gaSteam UG045
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENG
Index Parameter Description
Ec24 Burner 2 settings
Set pre-purge speed, minimum speed and maximum speed for rated
steam production
Ec25 Burner 3 settings
Set pre-purge speed, minimum speed and maximum speed for rated
steam production
7.4.12 Burner calibration
Also see the chapter Preparing for operation”.
The Burner Calibration submenu is used to access the procedure for configuring and calibrating the
burners on the humidifier.
Two types of gas can be selected:
l Natural gas (G20-G25);
l LPG (G30-G31).
Note: on selecting the type of gas, the humidifier automatically sets all the control parameters for
correct operation with that specific family of gas.
Index Parameter Description
Ec28 Burners calibration
Start the procedure to calibrate the burners. Follow the instructions
shown on the display
Guided calibration is a step-by-step procedure that helps the installer correctly set up the burner.
It is divided into three different steps:
1. Calibration at maximum fan speed (maximum output delivered by the humidifier);
2. Calibration at minimum fan speed (minimum output delivered by the humidifier=;
3. Verification of calibration at maximum output.
The first step once the type of gas has been selected; the humidifier will be switched on, if off, and
operated at the maximum output available. The screen will show info on the unit operating status, such as
pre-purge, fan speed and waiting. Wait for the humidifier to reach maximum output, then calibrate the
gas valve (see chap. Type of calibration), adjusting it so that the percentage of CO2 measured is within
the allowed range.
Repeat the operations for the other two steps, following the instructions shown on the screen, to
complete the calibration procedure.
Note:
l if an alarm is activated during calibration, the procedure stops and a warning message is shown;
l If during calibration no button is pressed for 5 minutes, the procedure will be interrupted and the
unit will return to normal operation.
7.5
Menu E. Settings
d.Master/Slave
7.5.1 Master/Slave system network settings (Installer menu)
To increase total production capacity when one single unit is not sufficient, the Master/Slave function can
be used to connect up to 20 units together in just one system. To set and enable the individual units in
the system, go to the Network” menu, specifically starting from screen Ed01.
Initial Master/Slave system configuration:
Index Parameter Description
Ed01 Master/Slave
Initial Master/Slave system configuration
Press PRG to configure the Master/Slave network
Ed02
Unit 1
Unit 2
-
-
Unit 20
Add unit to the Master/Slave system
To add a unit to the network enter the unit’s IP address. Scroll between
the units using the UP/DOWN buttons
Master/Slave system function configuration: from screen Ed07 (Master/Slave production) press PRG for
the following settings:
76|7. User menu and unit configuration
gaSteam - UG +0300090EN rel. 1.2 09.10.2018

Table of Contents

Related product manuals