to do this, access the “Network and sharing center” on the PC and go to “Local network connection”. Then
modify the addresses, as shown above, for Internet protocol version 4.
Each c.pHC controller can obviously also be added to the Ethernet local network, allowing the web server
to be accessed from any point in the network and for each humidifier.
Important: the controller is not accessible directly on the internet as a firewall guarantees remote
access only via a secure connection (Carel tERA cloud or encrypted VPN connection).
9.3
Web server
functions
The web server “Home” page provides access to the display, so as to carry out all the configuration
operations in the same way as if working directly on the unit. In addition, there will be an immediate
response from the unit on its display.
Fig.9.d
The main menus are:
l UNIT
l NETWORK
l MAINTENANCE
l INFO
Unit menu
Probes: information and configuration of the main and limit probe. Select the type of signal and define
the minimum and maximum values.
Wireless: enable and associate each wireless probe to the main probe group or limit probe group. Read
the humidity and/or temperature, level and battery status.
Control: select the control type. Set the set point, differential, minimum and maximum.
Configuration: set the time and date. Configure the main alarms and variation in percentages of fill and
drain times.
Scheduler: enable and set the daily and weekly time bands.
Network menu
Display a summary of the status of the units in the advanced Master/Slave system.
Maintenance
Timers: display boiler and unit operating hours. Display the time remaining until maintenance is required
and set the maintenance pre-alert.
Logs: display the log of main variables (production, set point, drain pump status, fill valve status, request,
unit status).
Live: real time display of the main variables (production, set point, drain pump status, fill valve status,
request, unit status).
Info
Unit info: information on the unit model and software version. Select language and unit of measure.
Resources: useful links (Carel website, gaSteam manuals and pages on Carel website).
Guide & FAQ: general information on using the web server.
Note: to avoid incorrect settings, some of the main unit operating parameters can only be modified
via the web server when the unit is off (off from keypad).
90|9. Web server
gaSteam - UG +0300090EN rel. 1.2– 09.10.2018