EasyManua.ls Logo

Carel gaSteam UG045 - Outlet Pressure Limits

Carel gaSteam UG045
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENG
l instructions provided in this chapter, the steam outlet hoses are aimed upwards and the distributor
has an upwards slope of at least ;
l any curves in the pipes or hoses are sufficiently wide (radius > 300 mm - 12 in) so as to not cause
bending or choking;
l the paths of the steam hose and condensate pipe comply with the instructions provided in this
chapter;
l the slope of the steam hose is sufficient to allow correct condensate drainage (> 2 for upward
sections,> for downward sections);
l the slope of the condensate drain pipe is at least at every point;
l the condensate drain pipe is fitted with a drain trap (filled with water before starting) to prevent
steam from escaping.
Fig.3.e Fig.3.f
Fig.3.g
3.7
Outlet pressure
limits
The back-pressure at the boiler outlet, either positive or negative, depends both on the relative pressure
in the duct/AHU and the pressure drop in the steam hose, due to bends or adapters, and the steam
distributor. Carel steam hoses have a pressure drop of around 150 Pa/m (0.021 psi) (in compliance with
the maximum flow-rate recommended by Carel). Carel DP* series linear distributors have a pressure
drop of around 25 Pa (0.003psi) (in compliance with the maximum flow-rate recommended by Carel).
Considering these values, the boiler outlet pressure must be:
l boiler outlet pressure > 150 [Pa/m]* steam hose length [m] + 25 [Pa] DP + pressure in duct/AHU [Pa]
Boiler outlet pressure values for gaSteam:
UG045 UG090 UG150 UG180 UG300 UG450
pressure limits at boiler outlet Pa (PSI) 0 to 2000 (0 to 0.290)
Tab.3.d
Note: a pressure of around -200 Pa (-0.029 psi) at the boiler outlet corresponds to around 20 mm
28|3. Steam distribution
gaSteam - UG +0300090EN rel. 1.2 09.10.2018

Table of Contents

Related product manuals