After having enabled the backup function, the unit that will start first in the event of simultaneous
activation can be selected.
Index Parameter Description
Ee02 Priority when starting
Define the priority of the units when in backup mode
Default: Disabled
Possible settings: Enabled/Disabled
The priority must be set to “YES” only on one of the two units; the “priority” parameter on the second
unit must be set to “NO”.
7.7
Menu E. Settings
- f. Manual mode
7.7.1 Manual mode (Service and Installer menu)
During first start-up or maintenance, “manual mode” may be useful in order to check the operation of the
main devices on the humidifier. Manual mode is only available when the unit is OFF and without any
active alarms. In addition, to safeguard the unit, the heaters can only be activated when there is water in
the boiler (high level, corresponding to green LED on)
Important: manual mode should only be activated by qualified personnel; improper use may cause
serious damage to the unit.
Index Description Parameter
Ef01
Manual
mode
Enable “Manual mode” to check operation of the individual components.
Default: Disabled
Possible settings: Disabled, manual outputs, manual production
Remarks: when exiting “Manual mode”, the settings are restored and normal
operation resumes automatically. If the user does not set any parameters in
the “Manual mode” menu for 30 minutes, manual mode is automatically
disabled.
Ef02 Manual management of outputs
Enable “Manual mode” to check operation of the individual components.
Test fill valve
Test drain pump
Activate the blower relay
Ef03 Manual request management Manually set the production request.
7.8
Menu E. Settings
- g. Initialisation
7.8.1 Initial wizard (Service and Installer menu)
The Wizard menu, screen index Eg01, is used to initiate step-by-step programming of the parameters
required for commissioning the unit. Below are the steps included in the first start-up procedure (some
steps may not be displayed, if not necessary):
1/9 - Choose the model (only if the replacement controller is not configured);
2/9 - Water hardness: auto or user; defined;
3/9 - Manual water hardness setting;
4/9 - Control type;
5/9 – Select the main room probe type:
6/9 – Select the limit probe type;
7/9 - Set the limits for active probes;
8/9 - Set the drain to dilute cycles: auto or user-defined;
9/9 - Set manual drain to dilute cycles.
Index Parameter Description
Eg01 Wizard
Start the wizard for initial unit configuration
Set whether to display the wizard when next restarting
Default: wizard enabled: YES
For further information, see the paragraph “Activation sequence”.
78|7. User menu and unit configuration
gaSteam - UG +0300090EN rel. 1.2– 09.10.2018