7.1.3 Alarm thresholds
To check that the relative humidity measured by the probe transducer is within certain predefined
values, two alarm thresholds can be configured:
l high relative humidity alarm threshold, for both the main probe and limit probe;
l low relative humidity alarm threshold for the main probe.
On exceeding these thresholds, an alarm is activated and the corresponding relay contact on the main
control board is closed. Temperature thresholds can also be set.
From the system menu, enter the alarm thresholds menu:
Fig.7.c
Parameter Description
Alarm thresholds
Set alarm thresholds
Low humidity/temperature alarm threshold
High humidity/temperature alarm threshold
Limit humidity/temperature alarm threshold
Default:
low humidity/temperature: 0% rH / C (32°F);
high humidity/temperature: 100% rH / 100°C F);
humidity/temperature limit: 100% rH / 100°C F);
Range: 0-100
7.1.4 Scheduler menu
Parameter Description
Scheduler
Enable time bands
Default: time bands disabled
Fig.7.d
After having enabled the scheduler in the corresponding menu, the humidifier operating intervals can be
set for one day (24h) and for the whole week. A time band can be set with production disabled (OFF),
enabled (ON), or enabled with s specific set point (ON+SET). Setting the ON time band, the unit uses the
main set point configured. If setting ON+SET, the specific set point for the time band can be configured.
ENG
gaSteam - UG +0300090EN rel. 1.2 09.10.2018