Fig.4.q
The following probes can be connected:
CAREL probes for rooms DPWC111000
for air ducts DPDC110000, DPDC210000
for industrial applications DPPC210000
Tab.4.n
Note: third-party active probes can also be connected to the controller.
4.9
Control with
temperature
probes
The controller also allows autonomous temperature control, and can be connected to a temperature
probe TT. It performs complete control based on the temperature measured inside the controlled
environment.
Fig.4.r
Key:
TT Active temperature probe
RC Remote contact
Tab.4.o
CONTROL WITH ONE ACTIVE TEMPERATURE PROBE
l short-circuit terminals 7U and 8U (jumper) to enable production; alternatively connect terminals 7U –
8U to a remote contact (e.g.: switch, timer,...);
l connect the main active room probe to terminals 1U, 2U (GND) and 3U (+12Vdc);
l to enable control, set: