UOM UG045 UG090 UG150 UG180 UG300 UG450
air intake and flue gas exhaust
Tab.16.d
* value refers to combustion of natural gas (G20); Tab. 8.b
** m
3
St = dry gas at 1C and 1013.25 mbar atmospheric pressure;
***: using the specific KITNSTALL for USA.
16.2 Technical values of the flue gas according to useful heat input
fuel type natural gas (G20) natural gas (G25) propane (G31) butane (G30)
UG045 UG090 UG180 UG045 UG090 UG180 UG045 UG090 UG180 UG045 UG090 UG180
rated heat input 34.76/ 65.00/ 130.0/ 34.76/ 65.00/ 130.0/ 34.76/ 65.00/ 130.0/ 34.76/ 65.00/ 130.0/
(kW/l/h/BTU) 118.712 221.987 443.973 118.712 221.987 443.973 118.712 221.987 443.973 118.712 221.987 443.973
flue gas flow-
rate (kg/s)
0.0163 0.0303 0.0606 0.0167 0.03115 0.0623 0.0154 0.0283 0.0566 0.0147 0.0276 0.0551
flue gas
temperature °C
(°F)
135
(253)
170
(338)
165
(329)
123
(253)
175
(347)
163
(325)
123
(253)
175
(347)
165
(329)
123
(253)
175
(347)
163
(325)
CO2 percentage
in flue gas (%)
9.4 9.4 9.4 9.3 9.3 9.3 11.2 11.4 11.2 11.6 11.6 12
Tab.16.e
fuel type natural gas (G20) natural gas (G25)
UG150 UG300 UG450 UG150 UG300 UG450
rated heat input 108/ 216/ 324/ 108/ 216/ 324/
(kW/l/h/BTU) 368.511 737.023 1,106,000 368.511 737.023 1,106,000
flue gas flow-rate (kg/s) 0.048 0.096 0.144 0.0167 0.03115 0.0623
flue gas temperature °C (°F) 172 (342) 168 (334) 165 (329) 172 (342) 168 (334) 165 (329)
CO2 percentage in flue gas (%) 9.4 9.4 9.4 9.3 9.3 9.3
Tab.16.f
16.3 Steam hose models
humidifier model: UG045 UG090 UG150 UG180 UG300 UG450
steam outlet ø mm (in): 2x 40 (1.6") 2x 40 (1.6") 80 (3.1") 4x 40 (1.6") 2x 80 (3.1") 3x 80 (3.1")
maximum capacity kg/h (lb/h): 45 (99) 90 (198) 150 (330) 180 (396) 300 (661) 450 992()
1312367AXX
1312461AXX
NORTH AMERICAN MARKET ONLY
SHOSE00040
1312461AXX
Tab.16.g
16.4 Linear distributor models and typical installations
gaSteam
humidifier outlet ø mm 2x 40 (2x 1.6”)
80
(3.1")
4x 40
(4x
1.6”)
2x 80
(2x
3.1")
3x 80
(3x
3.1")
humidifier capacity kg/h 45 90 150 180 300 450
distributor inlet
A) mm (in)
max. distributor
capacity kg/h
(lbs/h)
minimum width of
duct/AHU mm (in)
P/N UG045 UG090 UG150 UG180 UG300 UG450
ENG
gaSteam - UG +0300090EN rel. 1.2 09.10.2018