Increase the distance in the event of:
1. increased air speed in the duct;
2. less turbulence.
Mounting instructions (see the figure):
l drill a series of holes in the wall of the pipe, using the drilling jig of the distributor (found in the
packaging of the distributor);
l insert the distributor with the steam outlet holes facing upwards;
l fasten the distributor flange using four screws.
Fig.3.b
Key:
1. L-shaped mounting bracket (where featured)
2. flange gasket
3. steam inlet (ØA)
4. condensate drain (ØB)
5. flange screw (see technical leaflet supplied)
6. Ltot = total length from the support to the end of the pipe, including the cover (depending on the
model, see the paragraph “Linear distributors”);
o
Lact = actual length used (from the first to the last hole);
o
a = distance from the support to the first hole;
o
f = distance from the last hole to the end of the pipe;
1. slope (about 2°) for condensate drainage
2. diameter of the hole in the wall (ØY)
Dimensions - mm (in)
DP***D22R0 DP***D30R0 DP***D40R0
ØA 22 (0.9) 30 (1.2) 40 (1.6)
ØB 10 (0.4) 10 (0.4) 10 (0.4)
ØY 58 (2.3) 68 (2.7) 89 (3.5)
Ø 35 (1.4) 45 (1.8) 60 (2.4)
X 68 (2.7) 77 (3.0) 99 (3.9)
Tab.3.b
Length L
P/N L tot max kg/h lbs/hr
DP035D22R0 332 4 8.81
DP045D22R0 438 6 13.22
DP060D22R0 597 9 19.82
DP085D22R0 835 9 19.82
DP035D30R0 343 5 11.01