Index Parameter Description
Eh01
Unit supervision address
on BMS port
Set the unit’s supervision address and protocol for BMS port.
Default:
Address: 1;
Protocol: ModBus;
On/Off from SV: No;
Control from SV: No;
Possible settings:
Address: 1-247
Protocol: Modbus, BACnet, Carel
Address is the device’s supervision address on the BMS port. Enabling or disabling the parameters
On/Off from SV” and Control from SV” activates or deactivates the response to the corresponding signals
from the supervisor. For other supervisor protocols, select Carel protocol and use the Carel external
gateway (supernode for humidification).
7.9.2 BMS port (Installer menu)
Screen Eh02 is used to set supervisor communication on the BMS port.
Index Parameter Description
Eh02
BMS port configuration
settings
Set the communication parameters for supervision via BMS: Baud rate,
stop bits and parity
Default:
Baudrate: 19200
Stop bits: 2
Parity: None
7.9.3 BACnet MS/TP supervisor settings (Installer menu)
To set the address, maximum number of master units and maximum number of frames for BACnet MS/TP
supervision systems, use screen Eh03. The screen is only displayed when supervision is configured on the
BMS port with the BACnet protocol.
Index Parameter Description
Eh03
BACnet MS/TP
config
Set the address, maximum number of masters and maximum number
of frames
Default:
Address: 0
Max masters: 127
Max frames: 10
For BACNet MS/TP, in addition to setting the parameters in screen Eh03, it is also necessary to set the
parameter on screen Eh06.
Index Parameter Description
Eh06 Device inst. Default: 77000
7.9.4 Ethernet network (Installer menu)
To connect the unit to the local Ethernet network for operation in Master/Slave mode, software
Backup/Rotation or use the webserver, set the DHCP, IP, subnet mask, gateway and DNS parameters.
Important: these values must be provided by the local network administrator.
Index Parameter Description
Eh04 Ethernetnetwork settings
Set the unit's IP address for the Ethernet connection. Set DHCP, subnet
mask, gateway, DNS.
Default: