EasyManua.ls Logo

Carrier TRANSICOLD Vector 8700 - Page 149

Carrier TRANSICOLD Vector 8700
374 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7–11 62-12259
00017 High Compressor Discharge Temp
ACTIVATION: “Check Compressor Discharge Sensor” alarm not active (if alarm is active, refer to 00125
Check Compressor Discharge Sensor first) and: discharge temp rises above 285.1°F (140.6°C) for 30
seconds, or discharge temp rises above 295.0°F (146.1°C).
UNIT CONTROL: Engine Operation: Shutdown and alarm.
Electric Operation: Refrigeration system shutdown and alarm with PSCON still
energized.
RESET CONDITION: Auto Reset after 15 minutes when discharge temp falls below 266°F (130.0°C) or
alarm may be manually reset via Keypad or by turning the unit off, then back on again.
NOTE
Follow the steps below until a problem is found. Once a repair or correction has been made, the
active alarm should clear itself (refer to reset condition above). Operate the unit through the appro-
priate modes to see if any active alarm occurs. Continue with the steps below as necessary.
Corrective Actions:
1. Check Airflow Through Radiator / Condenser Coil
a. Inspect condenser / radiator fins. Fins must be straight. 90% or more of the coil surface must be
undamaged. No “dead” air spaces. Condenser / Radiator coil must be clean (refer to Section
8.5.11).
b. Check condenser airflow. Even airflow through the entire coil, with no “dead” spots.
c. Check condenser fan rotation / operation. Fans should operate correctly. Air should be drawn in
through the grill, and directed into the engine compartment.
2. Check LIV, CSMV, EVXV and ECXV - Clear Active Alarm list, then run Pretrip and check for any new
alarms. Any active alarms must be corrected and cleared before proceeding.
3. Check for Low Refrigerant Charge - Check refrigerant level in the receiver. Refer to Section 8.6.2.
Generally, level should be between upper and lower sight glasses with a refrigerated compartment tem-
perature of 35°F (1.0°C) or lower.
4. Check System Pressures - Install manifold gauge set and check and compare compressor discharge
and suction pressures with those shown on the microprocessor display. Suction and Discharge Pres-
sures must have the same reading on gauges and on microprocessor display. Pressures must be in the
normal range for ambient and refrigerated compartment temperature conditions.
5. Check Compressor - Check compressor for excessive vibration or noise. Replace compressor. Refer to
Section 8.7.
6. Check System for Noncondensable - Check refrigeration system for noncondensable gas(es). No non-
condensable gas(es) may be present. Refer to Section 8.6.2.

Table of Contents

Related product manuals