4–5 62-12259
4.5.1 Start-Stop Configuration
Start-Stop Operation is dependent on both Configuration and Functional Parameter settings. The first setting to be
considered is the START-STOP PARAMETERS Configuration. This setting determines control actions when in the
Perishable Range or Frozen Range. The available settings are TOGETHER and SEPARATE.
• When SEPARATE is chosen the control action will be different, depending on whether the setpoint is in the
Perishable Range or in the Frozen Range (refer to Section 4.6.1).
• When TOGETHER is chosen, the same settings apply to any setpoint.
If TOGETHER is selected, then the following Functional Parameter values will be available for use:
• MINIMUM RUN TIME
• MINIMUM OFF TIME
• RESTART TEMPERATURE
• OVERRIDE TEMP
• MAXIMUM OFF TIME
• FROZEN SHUTDOWN OFFSET
If SEPARATE is selected, then the following Functional Parameter values will be available for use:
• PERISHABLE MINIMUM RUN TIME
• PERISHABLE MINIMUM OFF TIME
• PERISHABLE RESTART TEMPERATURE
• PERISHABLE OVERRIDE TEMP
• PERISHABLE MAXIMUM OFF TIME
• FROZEN MINIMUM RUN TIME
• FROZEN MINIMUM OFF TIME
• FROZEN RESTART TEMPERATURE
• FROZEN OVERRIDE TEMP
• FROZEN MAXIMUM OFF TIME
• FROZEN SHUTDOWN OFFSET
NOTE
In the event that this Configuration was set to SEPARATE and the eleven Functional Parameters for
Perishable and Frozen have been set and the Configuration is changed from SEPARATE to
TOGETHER, the values from the Perishable settings will be the ones that will be used.