4.5.1 Start-Stop Configuration
Start-Stop Operation is dependent on both Configuration and Functional Parameter settings. The first setting to be
considered is the START-STOP PARAMETERS Configuration. This setting determines control actions when in the
Perishable Range or Frozen Range. The available settings are TOGETHER and SEPARATE.
When SEPARATE is chosen the control action will be different, depending on whether the setpoint is in the
Perishable Range or in the Frozen Range (refer to Section 4.6.1).
When TOGETHER is chosen, the same settings apply to any setpoint.
If TOGETHER is selected, then the following Functional Parameter values will be available for use:
MINIMUM RUN TIME
MINIMUM OFF TIME
RESTART TEMPERATURE
OVERRIDE TEMP
MAXIMUM OFF TIME
FROZEN SHUTDOWN OFFSET
If SEPARATE is selected, then the following Functional Parameter values will be available for use:
PERISHABLE MINIMUM RUN TIME
PERISHABLE MINIMUM OFF TIME
PERISHABLE RESTART TEMPERATURE
PERISHABLE OVERRIDE TEMP
PERISHABLE MAXIMUM OFF TIME
FROZEN MINIMUM RUN TIME
FROZEN MINIMUM OFF TIME
FROZEN RESTART TEMPERATURE
FROZEN OVERRIDE TEMP
FROZEN MAXIMUM OFF TIME
FROZEN SHUTDOWN OFFSET
NOTE
In the event that this Configuration was set to SEPARATE and the eleven Functional Parameters for
Perishable and Frozen have been set and the Configuration is changed from SEPARATE to
TOGETHER, the values from the Perishable settings will be the ones that will be used.