Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
69
– The current space temperature. D: _°F/C
– A calibration offset value to allow the local space
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
D:
R:
0
°F/C
-9.9 to 10 °F
(-5.5 to 5.5
°C)
– Displays the value read from a local RH sensor connected to one of the
hardware input channels.
R: 0 to 100%
– Displays the value read from a local CO
2
sensor connected to one of the
hardware input channels.
R: 0 to 5000ppm
Displays the value read from an outdoor CO
2
sensor connected to one of
the hardware input channels.
0 to 5000ppm
– Displays the current supply air temperature. R: -56 to 245°F
(-48.9 to 118.3°C)
Supply Air Temp Calibration
– A calibration offset value to allow the supply air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
D:
R:
0
°F/C
-9.9 to 10 °F
(-5.5 to 5.5
°C)
– The current outdoor air temperature. R: -56 to 245°F
(-48.9 to 118.3°C)
Outdoor Air Temp Calibration
– A calibration offset value allows the outdoor air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
D:
R:
0°F/C
-9.9 to 10
°F
(-5.5 to 5.5
°C)