100
Where
the
stop
valve
is
enclosed
in
a
room
with
a
door
the
sign
shall
be
fixed
on
the
outside
of
the
door,
and
a
second
sign,
bearing
the
words
«
Keep
locked
shut
»
shall
be
fixed
on
the
inside
of
the
door.
The
second sign
shall
be
circular
with
white
letters
not
less
than
5mm
high,
on
a
blue
background.
16.2.3 Control valve set
16.2.3.1 General
Where
the
sprinkler
system
comprises
more
than
one
installation
each
control
valve
set
shall
be
prominently marked
with
the
number
identifying
the
installation
it
controls.
16.2.3.2 Fully calculated installations
In
fully
calculated
installations
a
durable
notice
shall
be
fixed
to
the
rise
pipe
next
to
each
control
valve
set. The
notice
shall
include
the
following
information:
a)
the
installation
number;
b)
the
hazard
classification
or
classifications
of
the
areas
protected
by
the installation;
c)
for
each
hazard
class
area
within
an
installation:
1)
the
design
requirements
(area
of
operation
and
density
of
discharge);
2)
the
pressure-flow
requirement
at
the
'C'
gauge
or
flow
test
facilities
for
the most
unfavourable
and
most
favourable
areas
of
operation;
3)
the
pressure-flow
requirement
at
the
pump
delivery
pressure
gauge
for
the most
unfavourable
and
most
favourable
areas
of
operation;
4)
the
height
of
the
highest
sprinkler
above
the
level
of
the
'C'
gauge;
5)
the
height
difference
between
the
'C'
gauge
and
the
pump
delivery
pressure gauge.
16.2.4 Water supply connections to other services
Stop
valves
controlling
water
supplies
from
sprinkler
system
supply
pipes
or
trunk
mains
to
other
services
shall
be
appropriately
labelled;
e.g.
‘Fire fighting
hose
reels’,
‘Domestic
water
supply’
etc.
The labels
shall
have
raised
or
embossed
lettering
and
be
fixed
to
stop
valves
to
inhibit
unauthorised
removal.
16.2.5 Suction and booster pumps
16.2.5.1 Pre-calculated installations
A
nameplate
shall
be
fixed
to
each
suction
or
booster
pump,
carrying
the
following
information:
a)
the
output
pressure,
and
the
corresponding
rated
speed
and
flow
(l/min),
in
bar
at
the
inlet
condition
and
flow
rating
specified
in
table
18;
b)
the
maximum
power
absorbed
at
the
relevant
speed
at
any
value
of
flow.