K.9 Protection of racks with solid shelves and gangways storing plastic boxes
This
section
covers
the
protection
of
racks
with
solid
shelves
and
gangways.
The
gangways
shall
be
solid.
a
gap
of
0.1
m
is
allowed
between
the
rack
and
the
gangway
for
ventilation
purposes.
This
concept
is
based
on
fire
tests
and
shows
one
possible
solution
to
provide
adequate
protection.
K.9.1 Sprinkler arrangement in rack
Sprinklers
shall
be
arranged
under
the
gangways
at
the
outside
of
the
racks
at
a
distance
of
approx.
0.15
m from
the
face
of
the
racks
(see
figure
K1).
The
horizontal
sprinkler
distance
parallel
to
the
rack
and
along
the gangway
shall
be
1.8
m
max.
with
one
sprinkler
min.
between
two
rack
posts.
The
following
figure
shows the
sprinkler
arrangement.
§

gangway
gap for
ventilation
sprinkler
P

Table of Contents