EasyManua.ls Logo

CEA 4001 - Intermediate Sprinklers in High Hazard Occupancies

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
81
The sprinklers
in
the
region
of
the
opening
shall
be
capable
of
providing
the
minimum
flow
rate
for
sprinklers
in
the
rest
of
the
ceiling
protection.
For
hydraulic
calculation
purposes,
only
the
sprinklers
on
the
longer
side
of the
opening
need
be
considered.
11.4.11 Vertical shafts and chutes
At
least
one
sprinkler
shall
be
installed
at
the
top
of
all
shafts
except
where
the
shaft
is
incombustible
and inaccessible
and
contains
no
combustible
materials
except
electrical
cabling.
In
shafts
with
combustible
surfaces,
sprinklers
shall
be
installed
at
each
alternate
floor
level
and
at
the
top
of any
trapped
section.
11.4.12 Ceiling obstructions
The
use
of
suspended
ceiling
material
below
the
sprinklers
is
not
allowed
unless
the
material
has
been
shown not
to
impair
sprinkler
protection.
Where
sprinklers
are
fitted
below
suspended
ceilings,
the
ceiling
material
shall
be
of
a
type
which
has
been shown
not
to
be
subject
to
partial
collapse
under
incipient
fire
conditions.
11.4.13 Suspended open ceilings
Suspended
open
ceilings,
i.e.
ceilings
having
a
regular
open
cell
construction
recurring
throughout
their design,
may
be
used
beneath
LH
and
OH
sprinkler
systems
not
involving
storage
areas
where
the
following conditions
are
met:
-
the
total
plan
open
area
of
the
suspended
open
ceiling,
including
light
fittings, shall
not
be
less
than
70%
of
the
ceiling
plan
area;
-
the
minimum
dimension
of
the
ceiling
openings
shall
be
no
less
than
0,025m
or no
less
than
the
vertical
thickness
of
the
suspended
ceilings,
whichever
is
the greater;
-
the
structural
integrity
of
the
ceiling
and
any
other
equipment,
such
as
light fittings
within
the
volume
above
the
suspended
ceiling,
shall
not
be
affected
by operation
of
the
sprinkler
system.
sprinklers
shall
be
installed
as
follows:
-
sprinkler
spacing
above
the
ceiling
shall
not
exceed
3m;
-
vertical
separation
between
any
conventional
or
spray
sprinkler
deflector
and the
top
of
the
suspended
ceiling
shall
not
be
less
than
0,8m.
This
distance
may be
reduced
to
0,3m
if
flat
spray
sprinklers
are
used;
-
supplementary
sprinklers
shall
be
provided
to
discharge
below
light
fittings
or similar
obstructions
exceeding
0,8m
in
width.
Where
obstructions
within
the
ceiling
void
are
likely
to
cause
significant
interference
of
the
water
discharge they
shall
be
treated
as
walls
for
the
purpose
of
sprinkler
spacing.
11.5 Intermediate sprinklers in High Hazard occupancies

Table of Contents