90
the following
ways:
a)
with
a
suitable
corrosion
resistant
coating
applied
by
the
manufacturer;
b)
with
a
petroleum
jelly
coating
applied
once
before
and
once
after
installation.
The
anti-corrosion
treatment
shall
not
be
applied
to
sprinkler
bulbs.
1
13 Valves
13.1 Control Valve Set
Each
installation
shall
have
a
control
valve
set.
13.2 Stop Valves
All
normally
open
stop
valves
which
may
cut
off
the
water
supply
to
the
sprinklers
shall:
-
close
in
the
clockwise
direction;
-
be
fitted
with
an
indicator
that
clearly
shows
whether
it
is
in
the
open
or
closed
position;
-
be
secured
in
the
open
position
by
a
strap
and
padlock
or
secured
in
an
equivalent
manner.
NOTE
1:
no
stop
valves
are
allowed
downstream
of
the
control
valve
set
except
as
stated
elsewhere
in
these rules.
Stop
valve
downstream
of
the
control
valve
set
should
be
avoided,
where
possible.
Where stop
valves
are
installed
downstream
of
the
control
valve
set,
they
shall
be
monitored
electrically.
NOTE
2:
in
locations
such
as
high-rise
buildings,
where
high
static
pressures
are
likely,
special
care
should
be
taken
to
ensure
that
all
stop,
test,
drain
and
flushing
valves
are
suitable
for
the
installation pressures.
13.3 Ring main valves
Where
sprinkler
systems
are
fed
by
a
ring
main
supply
pipe
arrangement
on
the
premises,
valves
shall
be installed
to
isolate
the
ring
into
sections,
in
such
a
way
that
no
section
shall
include
more
than
4
control
valve sets.
13.4 Drain valves
Drain
valves
shall
be
fitted
as
specified
in
Table
27
to
allow
drainage
from:
a)
immediately
downstream
of
the
control
valve
set
or
of
its
downstream
stop
valve
where
such exists;
b)
immediately
downstream
of
any
subsidiary
alarm
valve;
c)
immediately
downstream
of
any
subsidiary
stop
valve;
d)
between
a
dry
pipe
or
subsidiary
control
valve
set
and
any
subsidiary
stop
valve
installed
for testing;

Table of Contents