130
A
Annex F
Special Requirements for Life Safety Systems
F.1 Subdivision into zones
Installations
shall
be
subdivided
into
zones,
in
accordance
with
Annex
D,
with
a
maximum
of
200
sprinklers per
zone.
F.2 Wet Pipe Installations
Sprinkler
installations
for
life
safety
shall
be
of
the
wet
pipe
type
and
any
subsidiary
dry
pipe
or
alternate extension
shall
comply
with
10.5.
F.3 Sprinkler type and sensitivity
Conventional,
Spray
or
Sidewall
sprinklers
shall
be
used.
The
sensitivity
shall
be
Quick
response,
except
that
Standard
‘A’
and
Special
response
may
be
used
in
rooms
not
less
than
500m²
in
area
or
not
less
than
5m
in
height.
F.4 Installation Main Control Valve Set
During
servicing
and
maintenance
of
the
installation
alarm
valves,
the
sprinkler
installation
shall
be
fully operational
in
all
aspects.
NOTE:
in
some
countries
duplicate
installation
control
valve
sets
are
required.
F.5 Water Supplies
The
system
shall
have
at
least
one
superior
single
water
supply.
NOTE:
in
some
countries
duplicate
supplies
are
required
for
life
safety
systems.
F.6 Theatres
National
requirements
shall
be
taken
into
consideration.
In
theatres
with
separated
stages
(i.e.
where
there
is
a
safety
curtain
between
the
stage
and
auditorium)
the safety
curtain
shall
be
provided
with
a
line
of
drenchers
controlled
by
a
quick
opening
valve
(e.g.
a
plug valve)
fitted
in
an
accessible
position.
The
water
supply
for
the
drenchers
shall
be
taken
upstream
of
any control
valve
set.
The
stage
shall
be
protected
by
a
water
spray
installation
with
automatic
and
manual activation.
Alternatively,
stages
with
a
total
height
no
greater
than
12m
may
be
protected
by
sprinklers.
All
workshops,
dressing
rooms,
scenery,
storerooms
and
spaces
below
the
stage
shall
be
sprinklered.
F.7 Additional precautions for maintenance
Only
one
zone
of
a
multi-zone
installation
shall
be
shut
down
at
a
time.
An
installation
or
zone
shall
be
shut down
for
the
minimum
time
necessary
for
maintenance.
The
partial
or
complete
shut-down
of
a
life
safety
sprinkler
installation
shall
be
avoided
wherever
possible. Only
the
smallest
part
of
the
installation
necessary
shall
be
isolated.