54
T
Table 14: Minimum width of settling chambers, suction pits, open channels and weirs
0,25m
<
d*
<
0,5m
0,5m
<
d*
<
1,0m
d*
<
1,0m
width
m
maximum
flow l/min
width
m
maximum
flow l/min
width
m
maximum
flow l/min
0,088
0,125
0,167
0,215
0,307
0,334
0,410
0,500
0,564
0,750
1,110
1,170
1,500
2,000
4,500
280
497
807
1
200
2
060
2
340
3
160
4
190
4
950
7
260
12
050
12
800
17
380
24
400
60
300
0,082
0,112
0,143
0,176
0,235
0,250
0,291
0,334
0,361
0,429
0,527
0,539
0,600
0,667
0,819
1,000
522
891
1
380
1
960
3
160
3
510
4
480
5
590
6
340
8
310
11
420
11
820
13
900
16
270
21
950
29
170
0,078
0,106
0,134
0,163
0,210
0,223
0,254
0,286
0,306
0,353
0,417
0,425
0,462
0,500
0,581
0,667
2,000
993
1
690
2
590
3
630
5
650
6
260
7
830
9
580
10
750
13
670
18
070
18
640
21
410
24
400
31
140
38
910
203
300
*
Dimension
d
in
Figure
5.
NOTE
:
for
dimensions
not
included
in
this
table,
the
conduit
shall
be
designed
such
that
the
water
vel
ocity
does
not
exceed
0,2m/s.
Two
screens
shall
be
provided,
with
one
in
use
and
the
other
in
a
raised
position
ready
for
interchange
when
cleaning
is
necessary.
8.4.1.6
Where
the
suction
inlet
draws
from
a
walled
off
area
of
the
bed
of
the
river,
canal,
lake
etc.,
the
wall
itself
shall
be
extended
above
the
water
surface
with
an
aperture
screening
arrangement.
Alternatively,
the
space
between
the
top
of
the
wall
and
the
water
surface
shall
be
enclosed
with
a
screen.
Screens
shall
be
as
specified
in
8.4.1.4.
8.4.1.7
Excavation
of
the
bed
of
the
lake
etc.,
to
create
the
necessary
depth
for
a
pump
suction
inlet
is
not recommended,
but
if
unavoidable
the
area
shall
be
enclosed
with
the
largest
screen
practicable,
but
in
any case
having
sufficient
clear
area
as
specified
in
8.4.1.4.
8.5 Pressure tanks
8.5.1 General
A
pressure
tank
is
a
tank
containing
water
under
air
pressure
which
shall
be
sufficient
to
ensure
that
all
the
water
can
be
discharged
at
the
necessary
pressure.
The
pressure
tank
shall
be
reserved
solely
for
the
sprinkler
system.
The
pressure
tank
shall
be
easily
accessible
for
external
and
internal
inspection.
It
shall
be
protected
against
corrosion
both
internally
and
externally.
The
discharge
pipe
shall
be
situated
at
least
0,05m
above
the
bottom
of
the
tank.
8.5.2 Housing