67
be
visually
and
audibly
indicated
at
a
location
normally
attended
by
responsible
personnel.
9.8.6.3
The
visual
fault
indication
shall
be
yellow.
The
audible
signals
shall
have
signal
strength
of
at
least
75dB
and
shall
be
able
to
be
silenced.
9.8.6.4
A
lamp
test
for
checking
the
signal
lamps
shall
be
provided.
9.9 Diesel engine driven pumps
9.9.1 General
A
diesel
engine
shall
be
capable
of
operating
continuously
at
full
load
at
site
elevation
with
a
rated
output
in
accordance
with
ISO
3046-1:1986.
The
pump
shall
be
fully
operational
within
15
seconds
of
the
beginning
of
any
starting
sequence.
Horizontal
pumps
shall
have
a
direct
drive.
The
automatic
start
and
operation
of
the
pumpset
shall
not
depend
on
any
energy
sources
other
than
the engine
and
its
batteries.
9.9.2 Engines
The
engine
shall
be
capable
of
starting
at
an
engine
room
temperature
of
5°C.
It
shall
be
provided
with
a
governor
to
control
the
engine
speed
to
±
5%
of
its
rated
speed
under
normal
load conditions,
and
be
constructed
so
that
any
mechanical
device
fitted
to
the
engine
which
could
prevent
the engine
starting
automatically,
will
return
to
the
starting
position.
9.9.3 Cooling system
The
following
types
of
cooling
systems
are
acceptable.
a)
cooling
by
water
from
the
sprinkler
pump
directly
into
the
engine-cylinder
jackets
via
a
pressure
reducing
device
if
necessary,
in
accordance
with
the
manufacturer's
specification.
The
outlet
pipe
shall
be
open
so
that
the
discharge
water
is
visible;
b)
a
heat
exchanger,
where
the
water
is
taken
from
the
sprinkler
pump
via
a
pressure
reducing
device
if
necessary,
in
accordance
with
the
manufacturer's
specification.
The
outlet
pipe
shall
be
open
so
that
the
discharge
water
is
visible.
The
water
in
the
closed
circuit
shall
be
circulated
by
an auxiliary
pump
driven
by
the
engine.
If
the
auxiliary
pump
is
belt
driven,
there
shall
be
multiple belts
such
that
even
if
half
the
belts
are
broken,
the
remaining
belts
are
able
to
drive
the
pump.
The
capacity
of
the
closed
circuit
shall
conform
to
the
value
specified
by
the
engine
manufacturers;
c)
an
air
cooled
radiator
with
a
fan
multiple
belt
driven
from
the
engine.
If
half
the
belts
should break,
the
remaining
belts
shall
be
capable
of
driving
the
fan.
The
water
in
the
closed
circuit
shall be
circulated
by
an
auxiliary
pump
driven
by
the
engine.
If
the
auxiliary
pump
is
belt
driven,
there shall
be
multiple
belts
such
that
even
if
half
the
belts
are
broken,
the
remaining
belts
are
able
to drive
the
pump.
The
capacity
of
the
closed
circuit
shall
conform
to
the
value
specified
by
the engine
manufacturers;
d)
direct
air
cooling
of
the
engine
by
means
of
a
multiple
belt
driven
fan.
When
half
the
belts
are

Table of Contents