46
7.6.1 General
Use
the
test
facility
specified
in
clause
7.4.
Test
each
supply
to
the
installation
independently
with
all
other
supplies
isolated.
7.6.2 Storage pump and pressure tank supplies
Fully
open
the
stop
valves
controlling
the
flow
from
the
supply
to
the
installation.
Open
the
installation drain
and
test
valve
fully
and
check
that
pump(s)
if
fitted
start
automatically.
Check
that
the
flow
is
as specified
in
clause
6.3
and
that
recorded
during
the
commissioning
test.
Record
the
supply
pressure measured
on
the
C
gauge.
C
ompare
this
with
the
appropriate
value
specified
in
clause
6.3
and
the
value recorded
during
the
commissioning
test.
7.6.3 Town main, booster pump, elevated private reservoir and gravity tank supplies
Fully open the stop valves controlling the flow from the supply to the installation. Open the drain and test
valve and check that the pump(s), if installed, have started automatically. Manipulate the drain and test
valve to give the appropriate flow specified in clause 6. When the flow is steady record the supply
pressure measured on the C gauge. Compare this with the appropriate value specified in clause 6
and the value recorded during the commissioning test.
7.7 Water contamination protection
Where a water contamination problem arises, consideration shall be given in accordance with
national regulation and/or the CEA recommendations given in the document entitled « Recommendations
for the Fire Protection of Stores Containing Hazardous Substances ».
T
Table 9: Connections for water for other services in low rise systems
Water
supply
type
Acceptable
number,
size
and
purpose
of
connection(s)
Town
main.
Main
and
supply
pipe
not
less than
100mm
one,
not
more
than
25mm
diameter,
for
non-industrial
use
Town
main.
Main
and
supply
pipe
not
less than
1
50mm
one,
not
more
than
40mm
diameter,
for
non-industrial
use or
one,
not
more
than
50mm
diameter,
for
fire
hose
ree
ls,
to
which may
be
made
a
further
connection
(close
to
the
first
connection, and
fitted
with
a
stop
valve
close
to
the
feed
end)
not
more
than
40m
m,
for
non-industrial
use.
Elevated
private
reservoir,
gravity
tank
or
automatic
pump
one,
not
more
than
50mm,
for
fire
hose
reels.
8 Choice of water supply
8.1 General
This
chapter
describes
the
various
water
supplies
and
combinations.
National
authorities
shall
determine
the
acceptabilities
of
these
in
respect
of
the
hazard
classifications
and
sprinkler
installation.