EasyManua.ls Logo

CEA 4001 - Action following sprinkler operation

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
104
of pipework
feeding
the
part
or
parts
where
work
is
taking
place;
g)
in
the
case
of
manufacturing
premises,
when
the
alterations
or
repairs
are
extensive,
or
it
is necessary
to
disconnect
a
pipe
exceeding
40mm
nominal
diameter,
or
to
overhaul
or
remove
a main
stop
valve,
alarm
valve
or
check
valve,
every
effort
shall
be
made
to
carry
out
the
work while;
h)
any
pump
which
is
out
of
commission
shall
be
isolated
by
means
of
the
valves
provided.
NOTE
:where
possible
parts
of
installations
should
be
reinstated
to
provide
some
protection
overnight
by
using
blinders
and
blanks
within
the
pipework;
the
blinders
and
blanks
should
be
fitted
with
visible
indicator
tags
numbered
and
logged
to
aid
timely
removal.
18.1.3.2 Planned shut-down
Only
the
user
shall
give
permission
for
a
sprinkler
installation
or
zone
to
be
shut
down
for
any
reason
other than
an
emergency.
Before
a
system
is
wholly
or
partly
shut
down
every
part
of
the
premises
shall
be
checked
to
ensure
that
there
is
no
indication
of
fire.
Where
premises
are
subdivided
into
separate
occupancies
constituting
buildings
in
communication
or
at
risk, protected
by
common
sprinkler
systems
or
installations,
all
occupiers
shall
also
be
advised
that
the
water
is
to
be
turned
off.
Particular
attention
shall
be
given
to
situations
where
installation
pipework
passes
through
walls
or
ceilings where
these
may
feed
sprinklers
in
areas
needing
special
consideration.
18.1.3.3 Unplanned shut-down
When
an
installation
is
rendered
inoperative
as
a
matter
of
urgency
or
by
accident,
the
precautions
in
18.1.3.1 shall
be
observed
as
far
as
they
are
applicable
with
the
least
possible
delay.
The
authorities
shall
also
be notified
as
soon
as
is
possible.
18.2 Action following sprinkler operation
18.2.1 General
Following
shut-down
after
operation
of
an
installation,
the
operated
sprinkler
heads
shall
be
replaced
by
heads
of
the
correct
type
and
temperature
rating,
and
the
water
supply
restored.
Unopened
sprinklers
around
the
area
in
which
operation
took
place
shall
be
checked
for
damage
by
heat
or
other
cause
and
replaced
as
necessary.
The
water
to
an
installation
or
zone
of
an
installation
that
has
operated
shall
not
be
shut
off
until
all
fire
has been
extinguished.
The
decision
to
shut
down
an
installation
or
zone
which
has
operated
because
of
fire
shall
be
taken
only
by the
fire
service.
Components
removed
from
the
system
shall
be
retained
by
the
user
for
possible
examination
by
an
authority.