106
18.3.2.5 Diesel engine restarting test
Immediately
after
the
pump
start
test
of
18.3.2.4,
diesel
engines
shall
be
tested
as
follows:
a)
the
engine
shall
be
run
for
20
min,
or
for
time
recommended
by
the
manufacturer,
whichever
is
the greater;
the
engine
shall
then
be
stopped
and
immediately
restarted
using
the
manual
start
test button;
b)
the
water
level
in
the
primary
circuit
of
closed
circuit
cooling
systems
shall
be
checked.
Oil
pressure
(where
gauges
are
fitted),
engine
temperatures
and
coolant
flow
shall
be
monitored
throughout
the
test.
Oil
hoses
shall
be
checked
and
a
general
inspection
made
for
leakage
of
fuel,
coolant
or
exhaust fumes.
18.3.2.6 Lead acid batteries
The
electrolyte
level
and
density
of
all
lead
acid
cells
(including
diesel
engine
starter
batteries
and
those
for control
panel
power
supplies)
shall
be
checked.
If
the
density
is
low
the
battery
charger
shall
be
checked
and, if
this
is
working
normally
the
battery
or
batteries
affected
shall
be
replaced.
18.3.2.7 Fire brigade and remote central station alarm connection
The
equipment
for
automatic
transmission
of
alarm
signals
from
a
sprinkler
installation
to
a
fire
brigade
or remote
manned
centre
shall
be
checked
for:
a)
continuity
of
the
connection;
b)
continuity
of
the
connection
between
the
alarm
switch
and
the
control
unit.
NOTE:
the
testing
procedure
shall
be
agreed
with
the
alarm
signal
recipient.
18.3.2.8 Trace heating and localised heating systems
Heating
systems
to
prevent
freezing
in
the
sprinkler
system
shall
be
checked
for
correct
function.
18.3.3 Special consideration
The
specific
gravity
of
the
anti-freeze
solution
shall
be
verified
quarterly
for
permanent
cold
storage
and yearly,
before
winter
for
unheated
areas.
18.4 Service and maintenance schedule
18.4.1 General
18.4.1.1 Procedures
In
addition
to
the
schedule
given
in
this
clause
any
procedures
recommended
by
component
manufacturers shall
be
carried
out.
18.4.1.2 Records
Each
routine
of
the
schedule
shall
be
carried
out
by
a
competent
person
who
shall
provide
the
user