160
T
Table 54: Flammable liquids in metal drums (ST4) with a capacity >20 l and 208 l (K3)
Class
Properties
°C
Storage
methods
Intermediated
sprinkler
level
in
figure
10
(1)
configuration
Ceiling sprinklers
Density mm/
min
Area
of
operation
m
2
1
FP
>
100
on
side on
end
each
12th
tier each
6th
tier
10
10
450
2
FP
<
100
on
side on
end
each
6th
tier each
tier
25
10
450
3
FP
<
55
on
side on
end
each
3rd
tier each
tier
25
10
450
4
FP
<
21
on
side
or on
end
each
tier
25
450
NOTE:
(1)
Horizontal
distance
between
sprinklers
shall
not
exceed
1,9m.
NOTE:
(2)
Drums
shall
be
stored
at
a
height
of
one
drum
per
tier.
Table 55: Flammable liquids in metal drums (STl,ST5,ST6) with a capacity of 20 l (K4)
Class
Properties
°C
Storage
methods
Maximum
storage
height
Ceiling sprinklers
Density
mm/min
Area
of
operation
m
2
1
FP
>
100
ST1
ST5/6
5,5
4,6
10
7,5
450
2
FP
<
100
ST1
ST5/6
4,0
4,6
12,5
450
3
FP
<
55
ST1
ST5/6
1,5
2,1
12,5
450
4
FP
<
21
ST1
ST5/6
1,5
2,1
12,5
450
K.4 Pallets - idle
ldle
pallets
stored
in
solid
piles
or
on
pallets
shall
be
protected
with
ceiling
sprinklers
according
to
table

Table of Contents