EasyManua.ls Logo

CEA 4001 - Housing of Equipment for Water Supplies; Test Facility Devices; Pressure;Flow Tests on Water Supplies; Water Supply Pressure Test

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
c)
if
the
system
is
not
a
high
rise
system;
and
d)
if
the
system
is
not
protecting
a
multi-storey
building.
The
sprinkler
system
pumps
shall
be
separate
from
any
hydrant
system
pumps
unless
a
properly
designed
combined
water
supply
is
used
(see
8.6.4).
7.3 Housing of equipment for water supplies
Water
supply
equipment,
such
as
pumps,
pressure
tanks
and
gravity
tanks,
shall
not
be
housed
in
buildings
or
sections
of
premises
in
which
there
are
hazardous
processes
or
explosion
hazards.
7.4 Test facility devices
Sprinkler
installations
shall
be
permanently
provided
with
suitable
devices
for
measuring
pressure
and
flow for
checking
compliance
with
clauses
6.3
and
9.
7.4.1 At control valve sets
A
now
measuring
device
shall
be
installed
at
each
control
valve
set
except
in
the
following
cases:
a)
where
two
or
more
control
valve
sets
are
installed
together,
the
device
need
be
installed
only
at
the
hydraulically
most
remote
set,
or,
when
the
installations
belong
to
different
hazard
classes,
at
the
control
valve
set
which
requires
the
highest
water
flow;
b)
where
the
water
supply
is
by
an
automatic
pump
or
pumps,
the
flow
measuring
device
may be
installed
at
the
pumphouse.
In
all
cases,
the
appropriate
allowance
must
be
made
for
the
pressure
losses
between
the
water
source
and
the
control
valve
set(s)
using
the
calculation
methods
specified
in
G.1.
Adequate
facilities
shall
be
provided
for
the
disposal
of
test
water.
NOTE:
dry
or
alternate
control
valve
sets
(main
or
subsidiary)
may
have
an
additional
flow
test
valve
arrangement
of
unspecified
flow
loss
characteristic
fitted
below
the
control
valve
set,
downstream
of
the
main
stop
valve,
to
facilitate
informal
supply
pressure
testing.
Such
flow
test
valves
and
pipework
should
have
a
nominal
diameter
of
40
mm
for
LH
installations
and
of
50
mm
for
other
installations.
7.4.2 At water supplies
At
least
one
suitable
flow
and
pressure
measuring
arrangement
shall
be
permanently
installed
and
shall
be
capable
of
checking
each
water
supply.
The
testing
apparatus
shall
be
of
adequate
capacity
and
shall
be
installed
in
accordance
with
the manufacturer's
instructions.
Care
shall
be
taken
with
the
distance
from
valves
and
fittings.
The
apparatus shall
be
installed
in
a
frost-proof
area.
7.5 Pressure/flow tests on water supplies
For
both
precalculated
and
fully
calculated
installations,
the
water
supply
shall
be
tested
at
least
at
the
installation
maximum
flow
demand
(Q
max).
7.6 Water supply pressure test

Table of Contents