173
Note
7
The
values
given
for
a
maximum
ceiling
height
of
12,2m
shall
be
used.
L.1.4.4
ESFR
sprinklers
shall
only
be
installed
in
buildings
with
roofs
or
ceilings
which
:
a)
have
a
slope
not
exceeding
170mm/m.;
b)
are
continuous
and
have
no
permanent
opening;
c)
are
of
non-combustible
construction;
d)
withstand
an
upward
pressure
of
150
N/m
2
.
NOTE
1:
Where
the
roof
or
ceiling
slope
exceeds
170mm/m,
the
roof
or
ceiling
may
be
underdrawn with
a
false
ceiling
complying
with
(a)
to
(d)
above,
with
EFSR
sprinklers
located
below
the false
ceiling.
NOTE
2:
Typical
ceiling
materials
include
10
mm
gypsum
board,
corrugated
or
sheet
steel
and mineral
tiles.
NOTE
3:
Concealed
spaces
shall
comply
with
5.4.
L.1.4.5
The
following
example
of
storage
or
commodities
are
not
suitable
for
protection
by
ESFR
sprinklers:
-
certain
storages
which
exhibit
unusual
fire
characteristics
such
as
roll
tissue;
-
open-top
combustible
containers;
-
unusual
commodities
or
storage
arrangements
which
have
not
been
proven,
by
either testing
or
analysis,
to
be
appropriate
for
ESFR
sprinklers
protection;
-
warehouses
in
which
the
commodities
or
the
type
of
storage
are
unpredictable;
-
special
risks
which
are
described
in
Annex
K
(K1
aerosols,
K3
flammable
liquid
storages,
K5
spirituous
liquors
and
K7
storage
containers
fabricated
from
polypropylene
and polyethylene);
-
rubber
tyres.
L.2 Sprinkler System Design
L.2.1 General
L.2.1.1
Only
wet-pipe
systems
shall
be
used.
L.2.1.2
ESFR
protection
is
based
on
construction
without
roof
vents
or
other
roof
opening.
If
roof
vents
or
other
roof
openings
are
unavoidable,
they
shall
be
operated
manually.
Any
draft
curtains
used
in
conjunction
with
roof
vents
or
other
roof
openings
shall
be
limited
in
depth
and
located
with
respect
to sprinklers
so
that
distances
specified
in
Table
L3
are
complied
with.
Any
open
roof
vents
or
other
roof
openings
shall
be
closed
automatically
preferably
before,
but
in
no
case
more than
30
s
after,
the
operation
of
the
first
sprinkler.
L.2.1.3
The
clear
space
beneath
the
sprinkler
deflectors
shall
be
no
less
than
1m.
L.2.1.4
Skylights
shall
be
flush
to
the
ceiling
or
underdrawn
at
ceiling
level.
The
skylights
shall
be
capable
of
withstanding,
without
failure,
a
temperature
of
300°C
for
at
least
5min.
Where
powered
ventilation
is
employed,
the
building
shall
be
protected
by
an
approved
fire
alarm
installation.
The
powered
ventilation
shall
be
stopped and
any
dampers
closed
automatically
in
response
to
the
fire
detection
system
alarm
of
fire.