17.1 Commissioning tests
17.1.1 Pipework
All
installation
pipework
shall
be
hydrostatically
tested
for
not
less
than
2
hours,
to
a
pressure
of
not
less
than
15
bar,
or
1,5
times
the
maximum
pressure
to
which
the
system
will
be
subjected,
(both
measured
at
the
installation
control
valves),
whichever
is
the
greater.
Dry
pipework
shall
also
be
tested
pneumatically
to
a
pressure
of
not
less
than
2,5bar
for
not
less
than
24 hours.
Any
leakage
that
results
in
a
loss
of
pressure
greater
than
0,
15
bar
for
the
24
hours
shall
be corrected.
Any
faults
disclosed,
such
as
permanent
distortion,
rupture
or
leakage,
shall
be
corrected
and
the
test repeated.
NOTE:
if
climatic
conditions
do
not
allow
hydraulic
testing
to
be
carried
out
immediately,
it
should
be
carried
out
as
soon
as
conditions
permit.
17.1.2 Equipment
The
system
shall
be
tested
as
specified
in
18.3.2
and
18.4.2
(i.e.
making
the
tests
which
will
be
made
on
a
routine
weekly
and
quarterly
basis)
and
any
faults
shall
be
corrected.
17.1.3 Water supplies
Water
supplies
shall
be
tested
as
specified
in
7.5,
and
diesel
engine
driven
pumps
shall
be
tested
as
specified
in
18.3.2.5.
17.2 Completion certificate and documents
The
installer
of
the
system
shall
provide
the
user
with
the
following:
a)
a
completion
certificate
stating
that
the
system
complies
with
all
appropriate
requirements
of
these
rules,
or
giving
details
of
any
deviation
from
the
requirements;
b)
a
complete
set
of
operating
instructions
and
"asbuilt"
drawings
including
identification
of
all
valves
and
instruments
used
for
testing
and
operation
and
a
users
programme
for
inspection
and
checking
(see
18.3).
1
18 Maintenance
18.1 General
18.1.1 Programmed work
The
user
shall
carry
out
a
programme
of
inspection
ad
checks
(see
clause
18.3),
arrange
a
test,
service
and maintenance
schedule
(see
clause
18.4)
and
keep
appropriate
records
including
a
logbook
which
shall
be
held
on
the
premises.
If
it
is
required
by
the
authorities.
The
user
shall
have
the
test,
service
and
maintenance
schedule
carried