Annex N (informative)
Minimum water supply for all hazard classes shall be superior.
The exceptions are given in table 30 hereunder:
Hazard
Classes
Cumulated
number
of
sprinklers
per
Hazard
classes
Minimum
type
of
Water
supply
LH;
OH1
<
1000
Single
(2)
HHP
>
5000
Duplicate
HHS
>
3000
(1)
Duplicate
Note 1: 4000 if more than 1000 in-rack sprinklers.
Note 2: In premises for immobile persons (e.g. hospitals, children’s nurseries…), the minimum
is a superior water supply.
If the cumulated number of sprinklers connected to the same water supply is greater than 10.000 the
type of water supply shall be duplicated.