K.2 Clothes in multiple garment hanging storage
K.2.1 General
This
annex
describes
special
provisions
for
the
protection
of
intensive
hanging
garment
stores
having multiple
row
or
garment
racks
at
two
or
more
levels.
They
may
have
automatic
or
semi-
automatic
garment delivery,
picking
or
transportation
systems.
Access
to
elevated
garment
storage
levels
within
a
warehouse
is usually
by
walkways
and
ramps.
A
common
feature
of
hanging
garment
storage
is
that
there
is
no
fire separation
between
the
decks.
Walkways,
aisles,
ramps
and
garment
racks
create
a
significant
obstruction
to ceiling
level
sprinkler
protection.
Protection
of
hanging
garments
stored
in
carousels
or
vertical
blocks without
aisles
is
beyond
the
scope
of
this
annex.
K.2.2 Categorization
This
annex
applies
to
all
types
of
garments,
irrespective
of
their
storage
category.
K.2.3 Sprinkler protection
Each
garment
rack
shall
be
limited
to
two
rows
of
hanging
garments
(side
by
side)
and
a
storage
height
of
3,5m
between
intermediate
levels
of
sprinklers.
Each
rack
shall
be
separated
by
an
aisle
of
at
least
0,8m width.
The
garment
racks
shall
be
protected
by
a
single
row
of
sprinklers.
The
spacing
between
the
sprinkler rows
shall
not
exceed
3,0m.
The
sprinklers
installed
directly
above
the
garment
racks
shall
be
stagger
spaced
in
the
vertical
plane,
at horizontal
intervals
of
not
more
than
2,8m
along
the
length
of
the
rack.
There
shall
be
a
sprinkler
not
more than
1,4m
from
the
rack
end.
The
clearance
between
the
top
of
the
garments
and
the
sprinkler
deflector
shall
be
at
least
0,
15m.
Each
sprinkler
row
protecting
garment
storage
racks
should
be
capped
by
a
continuous
solid
horizontal
baffle
of
at
least
the
length
and
width
of
the
garment
row.
The
baffle
should
preferably
be
of
a
non-
combustible material.
The
upper
level
of
sprinkler
rack
protection
and
baffle
may
be
omitted
providing
the
clearance
between
the top
of
the
garments
and
the
deflectors
of
the
ceiling
sprinklers
does
not
exceed
3m
height.
Sprinklers
shall
be
installed
below
all
access
ramps,
main
aisles,
walkways
and
transportation
routes,
with the
exception
of
aisles,
not
exceeding
1,2m
wide,
between
sprinkler
protected
garment
storage
rows.
K.2.4 Sprinklers in operation
The
number
of
rack
sprinklers
assumed
to
operate
shall
be
as
follows:
Rows
:
3
Levels
:
3
Sprinklers
per
row
3
:
3
Where
there
are
more
than
3
levels
of
sprinkler
protection,
3
rows
of
3
sprinklers
on
3
protected
levels
shall be
assumed
to
operate.
Where
there
are
3
levels
or
less,
3
rows
of
3
sprinklers
should
be
assumed
to
operate
on
all
protected
levels.
K.2.5 Ceiling sprinklers