CEA 4001 - Flushing Connections; Pressure Gauges

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
92
c)
any
water
flow
alarm
switch
installed
downstream
of
the
main
control
valve
set.
The
test
valve shall
be
connected
downstream
of
the
water
flow
alarm;
d)
any
automatic
pump
starting
device;
e)
any
pump
or
pressure
tank
house
sprinkler
alarm
flow
switch
installed
upstream
of
the
control valve
set.
13.5.2 Remote test valves
A
test
facility
shall
be
provided,
incorporating
a
test
valve
with
any
associated
fittings
and
pipework, delivering
a
flow
equivalent
to
the
discharge
from
a
single
sprinkler,
connected
at
the
hydraulically
most remote
location
on
a
distribution
pipe.
13.6 Flushing connections
Flushing
connections,
with
or
without
permanently
installed
valves,
shall
be
fitted
on
the
spur
ends
of
the
installation
distribution
pipes.
They
shall
-
be
at
least
DN50
and
-
in
case
of
distribution
pipes
bigger
than
DN50
be
connected
eccentrically
at
the
bottom
of
the distribution
pipe
and
-
be
at
least
200mm
long
Flushing
connections
shall
be
fitted
with
a
suitable
plug
or
cap.
NOTE
1:
it
may
be
desirable
in
certain
cases
to
fit
flushing
connections
on
ranges,
e.g.
in
the
form
of
a blank
tee.
NOTE
2:
in
addition
to
their
use
for
flushing
of
the
pipework,
flushing
connections
may
be
used
to
check that
water
is
available
and
for
carrying
out
pressure
and
flow
tests.
NOTE
3:
pipework
which
is
completely
full
of
water
may
be
damaged
by
the
increase
in
pressure
due
to temperature
rises.
If
complete
venting
of
air
in
an
installation
is
likely
to
occur,
e.g.
in
the
case
of
a
gridded
layout
with
flushing
connections
at
the
extremities,
consideration
should
be
given
to
the fitting
of
pressure
relief
valves
or
expansion
vessels.
13.7 Pressure gauges
Pressure
gauge
scale
divisions
shall
not
exceed:
a)
0,2
bar
for
a
maximum
scale
value
less
than
or
equal
to
10
bar;
b)
0,5
bar
for
a
maximum
scale
value
greater
than
10
bar.
NOTE:
the
maximum
scale
value
should
be
of
the
order
of
150%
of
the
known
maximum
pressure
to
be applied.
13.7.1 Water supply connections
Each
town
main
connection
shall
be
fitted
with
a
pressure
gauge
between
the
supply
pipe
stop
valve
and